Precondition Access level 2 is activated.
The operating mode is displayed.
1. Open the 5.4
<Configuration – Operating modes> menu.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.4 Operating modes
Menu
▶3 External values control
------------------------------
Ramp up time
7s
Active line
Ramp down time:
7s
2. Use «Up» or «Down» to select the
Ramp up time line.
3. Press «Enter».
The setting mode is active.
4. Use «Up» or «Down» to set the time in seconds.
You can set this parameter in a range of 0–600 seconds.
5. Press the «Enter» key.
The setting is applied.
6. Set the value for the
Ramp down time: in the same manner.
7. Press «Escape» repeatedly to leave this menu.
Result The change speed for the speed is set.
8.7 Setting the machine for master control operation
8.7.1 Overview of the different master operating modes
The controller offers several possibilities to work together with other controllers:
Method
Description
Section
SIGMA AIR
MANAGER 4.0 mode
You must modify the settings in SIGMA CONTROL 2 for the op‐
eration via SIGMA NETWORK using the
KAESER SIGMA AIR MANAGEMENT SYSTEM (SIGMA AIR
MANAGER 4.0).
Master control via
communication module
For example, the controller (and therefore the machine) receives
the instruction LOAD or IDLE via the PROFIBUS master (e.g.
SIGMA AIR MANAGER).
Master control via re‐
mote contact
The machine is controlled by signals from a master controller.
Master control of two
machines in master/
slave operation
The two SIGMA CONTROL 2 controllers operate as master and
slave.
Tab. 66 Overview of the different master controllers
8
Initial Start-up
8.7
Setting the machine for master control operation
No.: 901700 14 E
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X
105