1. Hold the RFID Equipment Card supplied with the machine in front of the RFID reader.
Users are always logged in with access level 2.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
Log-in successful
Menu
Button to change password
Prompt for whether the password should be
changed
------------------------------
Name:
E00019895
Level:
2
2. Within 10 minutes, hold the teachable master RFID Equipment Card in front of the RFID read‐
er.
The master RFID Equipment Card is registered in the machine.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
Registration successful
The master RFID Equipment Card has been regis‐
tered
------------------------------
Name:
E00017326
Level:
2
3. Should you wish to register the master RFID Equipment Card for the other machines, repeat
the above steps in each machine.
Result You have now registered a master RFID Equipment Card in the machine.
8.2.8 Checking/setting the date and time
Precondition Access level 2 is activated
Checking/setting the time
➤ When operating the machine with a timer programme, check the time settings at least
once a year.
➤ The date and time can be synchronised automatically using a time server. In this case, it
is no longer necessary to set the time manually. See chapter 8.2.16.
1. Open the menu 5.1
<Configuration – General>.
2. Using the «Up» or «Down» key, select the line
Date/Time.
8
Initial Start-up
8.2
Setting the controller
No.: 901700 14 E
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X
55