After a fault occurs in the refrigerated dryer, the SIGMA CONTROL 2 will shut the machine down.
In order to ensure compressed air delivery for a defined period of time, the operator can activate
the "fault mode without refrigerated dryer" function. The quality of the compressed air (dried com‐
pressed air) is compromised in this case. The
0069 Error operation without RD → Call service!
warning message is displayed. The
0069 warning message remains active for the entire time of
operation in fault mode.
Precondition The operator decides: Compressed air quantity has a higher priority than the compressed air quali‐
ty
Access level 2 is activated.
The
< Configuration ➙ Refrigeration dryer > menu is selected.
1. Press «DOWN» repeatedly until
Error operation without RD is displayed as the active line.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.9 Refrigeration dryer
Menu
·········
Error operation without RD
Active line
active: ☐
Run time max.: 8h
Running time (fixed)
Actual
2. Press the «DOWN» key.
The check box for activation of the fault mode is displayed as the active line.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.9 Refrigeration dryer
Menu
·········
Error operation without RD
active: ☐
Active line
Run time max.: 8h
Running time (fixed)
Actual
3. Press «Enter» to switch into setting mode.
The
check box flashes.
4. Press «UP».
5. Press «Enter» to accept the setting.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.9 Refrigeration dryer
Menu
·········
Error operation without RD
active: ☑
Active line
Run time max.: 8h
Running time (fixed)
Actual
7
Initial Start-up
7.7
Activating the settings for the refrigerated dryer
9_9450 03USE
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3
81
Summary of Contents for ESD 352 SFC
Page 5: ......
Page 6: ......
Page 7: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 14: ......
Page 15: ......
Page 16: ......
Page 17: ......
Page 18: ......
Page 19: ......
Page 20: ......
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 25: ......
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 171: ...KKW SSC 2 03 en 01 BA SIGMA CONTROL FLUID KKW SSC 2 03 01 20130805 113302...
Page 173: ......
Page 175: ...Contents ii Quick user guide Controller SIGMA CONTROL 2 SCREW FLUID 1 1 3 9_9450 03 USE...
Page 215: ...Contents iv Service manual Controller SIGMA CONTROL 2 SCREW FLUID 1 1 3 9_9450 03USE...
Page 392: ...KKW GBASE 1 00 en ERSATZTEILE 10357405_10 ESD 2C 20130903 115349...