■ Assign and activate the input
■ Set the time delay
■ Set the logic
■ Assign and activate the output
■ Select the message type (operational, fault, warning)
■ Activate the message.
7.11.3.1 Selecting the < External messages > menu
Precondition Access level 2 is activated,
The electrical connections are made.
1. In operating mode, switch to the main menu with the «Enter» key.
2. Select
< Configuration ➙ I/O periphery ➙ External messages > (see Section 7.11.1.1)
The
External messages menu is displayed.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.7.3 External messages
Menu
▶1 External message 1
Active line with external message No. 1
▶2 External message 2
▶3 External message 3
▶4 External message 4
▶5 External message 5
▶6 External message 6
7.11.3.2 Entering the message text
External message 1 is shown as example.
1. Press «Enter».
External message 1 is displayed as the active line.
2. Press «Enter» to switch into setting mode.
The display of the character set flashes.
3. Enter the individual message text.
4. Press «Enter» to accept the setting.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.7.3.1 External message 1
Menu
External message 1
Message number
DI 1.11 ☐
No input assigned
td : 0 s ¦ Logic +
Logic
DOR 1.04 ☐
Warning ☑
Message type (operational, alarm, warning)
7.11.3.3 Assign and activate the input
1. Press «DOWN» repeatedly until "Input" is displayed as the active line.
7
Initial Start-up
7.11 Configuring input and output signals
130
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3
9_9450 03USE
Summary of Contents for ESD 352 SFC
Page 5: ......
Page 6: ......
Page 7: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 14: ......
Page 15: ......
Page 16: ......
Page 17: ......
Page 18: ......
Page 19: ......
Page 20: ......
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 25: ......
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 171: ...KKW SSC 2 03 en 01 BA SIGMA CONTROL FLUID KKW SSC 2 03 01 20130805 113302...
Page 173: ......
Page 175: ...Contents ii Quick user guide Controller SIGMA CONTROL 2 SCREW FLUID 1 1 3 9_9450 03 USE...
Page 215: ...Contents iv Service manual Controller SIGMA CONTROL 2 SCREW FLUID 1 1 3 9_9450 03USE...
Page 392: ...KKW GBASE 1 00 en ERSATZTEILE 10357405_10 ESD 2C 20130903 115349...