Undercounter Refrigerators and Freezers
PAGE 24
7. MIcRoPRocEssoR contRol
(cont.)
7R - VIEWInG sEnsoR tEMPERAtUREs:
These parameters allow a service technician or customer to view the temperature of all
sensors within the unit. The temperatures cannot be adjusted.
Follow the instructions to enter the customer access code on page 8. When the control
displays Thermostat Set Point High , press the up arrow key until the
display reads Cabinet Air Sensor Evaporator Coil Sensor or Disharge
Line Sensor or press the SET button . The display will read the
temperature of the designated sensor.
Press the UP or DOWN arrow keys to scroll through the parameters or press
the ALARM CANCEL button
to exit.
7q - sEttInG tHE AUdIBlE AlARM stYlE:
These parameters will allow the customer to turn on/off the audible alarm feature on the
Microprocessor control. The audible alarm is preset from the factory to OFF. The customer
can choose between an audible alarm that sounds for 3 seconds then automatically turns
off, or a continuous audible alarm that must be manually acknowledged. Regardless of
this feature’s setting, visual alarm text will display when conditions warrant.
To adjust this setting, follow the instructions to enter the customer access code on page
8. When the control displays
Thermostat Set Point High, press the up arrow
key until the display reads Audible Alarm Style. Press the set button .
The display will read OFF. Use the arrow keys to scroll between
for the 3-Second Audible Alarm Burst or for Continuous Audible Alarm.
When the display shows your choice of style, press the set button . The display
will then read thermostat Set Point High. Use the arrow keys to
scroll to the next parameter or press the Alarm Cancel Button to exit.
SET
SET
)
)
)
SET
SET
)
)
)