Electrical Control Function
Electrical Control System
130
1. Electrical Control Function
1.1 Abbreviation
T1: Indoor room temperature
T2: Middle indoor heat exchanger coil temperature
T2B: Indoor heat exchanger exhaust coil temperature
T3: Outdoor heat exchanger pipe temperature
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
1.2 Main Protection
1.2.1 Compressor Restart Delay
1.2.2 Temperature Protection of Compressor Discharge
When the discharge temperature of compressor rises, the running frequency is limited according to the
following rules:
12K/18K
24~60K
T 5
T 5
1.2.3 Indoor Fan Delayed Open Function
When the unit starts up, the louver is immediately active . The indoor fan opens 7 seconds later.
If the unit runs in heating mode, the indoor fan is also regulated by the anti-cold wind function.
1.2.4 Fan Speed Malfunction
For A6 Duct:
If a fault occurs on the air volume regulator or the regulator enters protection mode, it sends the error
message CF and an instruction to reduce fan speed to the master. The message and the instruction can be
inquired with the remote controller or the wired controller. (Fault and protection information are displayed for
one minute). After a fault occurs, the master unit shows the error code E3 and the fault count for one minute.
If the fault occurs three times, then the fan is unable to resolve the problem independently. External
shutdown by a remote controller, wired controller, or central controller must be used to clear the fan fault and
fault count. The fan runs normally for 5 minutes while clearing fault count.
C o m p r e s s o r o f f
F r e q u e n c y l i m i t
F r e q u e n c y h o l d i n g
N o r m a l
F
C o m p r e s s o r o f f
E
F r e q u e n c y l i m i t 1
D
F r e q u e n c y l i m i t 2
C
F r e q u e n c y h o l d i n g
B
F r e q u e n c i e s i n c r e a s e s l o w l y
A
N o r m a l
Summary of Contents for KOB30U-18HFN32
Page 1: ...i KAISAI SUPER DC INVERTER SERIES Service Manual 2019 ...
Page 12: ...Indoor Units 11 Service Space 3 Service Space 1000m m 1000mm 1000m m 1000m m ...
Page 15: ...Indoor Units 14 Wiring Diagrams ...
Page 20: ...Indoor Units 19 Air Velocity Distributions Reference Data 30 42K Cooling Heating ...
Page 21: ...Indoor Units 20 Air Velocity Distributions Reference Data 48 55K Cooling Heating ...
Page 26: ...Indoor Units 25 Field Wiring 10 Field Wiring KCD 24HRF32 KCD 36HRF32 ...
Page 27: ...Indoor Units 26 Field Wiring KCD 48HRF32 KCD 55HRF32 ...
Page 49: ...Indoor Units 48 Field Wiring 10 Field Wiring 18k 55k ...
Page 53: ...Indoor Units 52 Service Space 3 Service Space ...
Page 55: ...Indoor Units 54 Wiring Diagrams ...
Page 72: ...Indoor Units 71 Service Space 3 Service Space ...
Page 73: ...Indoor Units 72 Wiring Diagrams 4 Wiring Diagrams KCA3U 12HRF32X ...
Page 82: ...Outdoor Units Outdoor Units 82 10 Field Wiring KCA3U 12HRF32X ...
Page 87: ...Outdoor Units 87 Wiring Diagrams 3 Wiring Diagrams KOB30 12HFN32X ...
Page 88: ...Outdoor Units 88 Wiring Diagrams KOB30U 18HFN32 ...
Page 89: ...Outdoor Units 89 Wiring Diagrams KOCA30U 24HFN32 ...
Page 90: ...Outdoor Units 90 Wiring Diagrams ...
Page 91: ...Outdoor Units 91 Wiring Diagrams KOD30U 36HFN32 ...
Page 92: ...Outdoor Units 92 Wiring Diagrams ...
Page 93: ...Outdoor Units 93 Wiring Diagrams KOE30U 48HFN32 KOE30U 55HFN32 ...
Page 118: ...Installation 119 Refrigerant pipe installation ...
Page 183: ...Controller Electrical Control System 184 ...
Page 184: ...Controller Electrical Control System 185 ...