Electrical Control Function
Electrical Control System
138
1.3.11 Outdoor Unit Point Check Function(Excluding 12K&18K models)
A check switch is included on the outdoor PCB.
Push SW1 to check the unit's status while running. The digital display shows the following codes each time
the SW1 is pushed.
N
Display
Remark
00
Normal display
Displays running frequency, running state, or malfunction code
01
Indoor unit capacity demand code
Actual data*HP*10
If a capacity demand code is higher than 99, the digital display
shows single and double digits.
For example, if the digital display shows “5.0”, the capacity
demand is 15. If the digital
display tube shows “60”, the
capacity demand is 6.0.
02
Amendatory capacity demand code
03
The frequency after the capacity requirement
transfer
04
The frequency after the frequency limit
05
The frequency of sending to 341
06
Indoor unit evaporator outlet temperature
(heating T2
,
cooling T2B)
If the temperature is lower than -9
℃
, the digital display shows
“-9.” If the temperature is higher than 70
℃
, the digital display
shows “70.” If the indoor unit is not connected, the digital
display shows:
“――”
07
Condenser pipe temperature (T3)
08
Outdoor ambient temperature (T4)
09
Compressor discharge temperature (T5)
The display value is between 0
–129
℃
. If the temperature is
higher than 99
℃
, the digital display shows single and double
digits.
For example, if the digital display shows “0.5", the compressor
discharge temperature is 105
℃
.
If the digital display shows “1.6,” the compressor discharge
temperature is 116
℃
.
10
AD value of current
The display value is a hexidecimal number.
11
AD value of voltage
12
Indoor unit running mode code
Off:0, Fan only: 1,Cooling: 2, Heating: 3, Forced cooling: 4,
Dry: 6, Self-clean: 8, Forced defrosting: 10
13
Outdoor unit running mode code
Off:0, Fan only: 1,Cooling: 2, Heating: 3, Forced cooling: 4,
Dry: 6, Self-clean: 8, Forced defrosting:10
14
EXV open angle
Actual data/4.
If the value is higher than 99, the digital display shows single
and double digits.
For example, if the digital display shows “2.0", the EXV open
angle is
120×4=480p.
15
Frequency limit symbol
Bit7
Frequency limit
caused by IGBT
radiator
The display value is a
hexadecimal number. For
example,
the
digital
display show 2A, then
Bit5=1,
Bit3=1,
and
Bit1=1.
It means frequency limit
may be caused by T4, T3
or the current.
Bit6
Frequency limit
caused by PFC
Bit5
Frequency limit
caused by T4.
Bit4
Frequency limit
caused by T2.
Bit3
Frequency limit
caused by T3.
Bit2
Frequency limit
caused by T5.
Bit1
Frequency limit
caused by current
Bit0
Frequency limit
caused by voltage
16
DC fan motor speed
0
:
Off,
1: Turbo,
2: High,
3: Medium,
4: Low,
5:
Breeze, 6: Supper breeze
17
IGBT radiator temperature
The display value is between 0
–30
℃
. If the temperature is
higher than 99
℃
, the digital display shows single and double
Summary of Contents for KOB30U-18HFN32
Page 1: ...i KAISAI SUPER DC INVERTER SERIES Service Manual 2019 ...
Page 12: ...Indoor Units 11 Service Space 3 Service Space 1000m m 1000mm 1000m m 1000m m ...
Page 15: ...Indoor Units 14 Wiring Diagrams ...
Page 20: ...Indoor Units 19 Air Velocity Distributions Reference Data 30 42K Cooling Heating ...
Page 21: ...Indoor Units 20 Air Velocity Distributions Reference Data 48 55K Cooling Heating ...
Page 26: ...Indoor Units 25 Field Wiring 10 Field Wiring KCD 24HRF32 KCD 36HRF32 ...
Page 27: ...Indoor Units 26 Field Wiring KCD 48HRF32 KCD 55HRF32 ...
Page 49: ...Indoor Units 48 Field Wiring 10 Field Wiring 18k 55k ...
Page 53: ...Indoor Units 52 Service Space 3 Service Space ...
Page 55: ...Indoor Units 54 Wiring Diagrams ...
Page 72: ...Indoor Units 71 Service Space 3 Service Space ...
Page 73: ...Indoor Units 72 Wiring Diagrams 4 Wiring Diagrams KCA3U 12HRF32X ...
Page 82: ...Outdoor Units Outdoor Units 82 10 Field Wiring KCA3U 12HRF32X ...
Page 87: ...Outdoor Units 87 Wiring Diagrams 3 Wiring Diagrams KOB30 12HFN32X ...
Page 88: ...Outdoor Units 88 Wiring Diagrams KOB30U 18HFN32 ...
Page 89: ...Outdoor Units 89 Wiring Diagrams KOCA30U 24HFN32 ...
Page 90: ...Outdoor Units 90 Wiring Diagrams ...
Page 91: ...Outdoor Units 91 Wiring Diagrams KOD30U 36HFN32 ...
Page 92: ...Outdoor Units 92 Wiring Diagrams ...
Page 93: ...Outdoor Units 93 Wiring Diagrams KOE30U 48HFN32 KOE30U 55HFN32 ...
Page 118: ...Installation 119 Refrigerant pipe installation ...
Page 183: ...Controller Electrical Control System 184 ...
Page 184: ...Controller Electrical Control System 185 ...