Electrical Control Function
Electrical Control System
140
If the capacity demand is 0, the digital display shows “0”.
If the indoor unit is not connected, the digital display shows:
“――”
Appendix
Shutdown Causes
Code
Frequency limit caused by current
1
Frequency limit caused by T2 in cooling
2
Frequency limit caused by T2 in heating
3
Preset temperature reached
4
Frequency limit caused by T4
5
Defrosting
6
Mode switching
7
High discharge temperature protection
9
High evaporator coil temperature T2 protection
10
Evaporator low temperature T2 protection
11
Condenser high temperature T3 protection
12
Low indoor room temperature protection in drying mode
13
Low
ambient
temperature protection
14
Refrigerant leakage detection
15
Communication malfunction between indoor and outdoor units
16
Communication error between outdoor main chip and compressor driven chip IR341
17
AC power input voltage protection
18
Top temperature protection of compressor
19
Outdoor EE Malfunction
20
Fan speed malfunction
21
Temperature sensor open or short circuit
22
Overcurrent protection
23
IMP overcurrent protection
24
Compressor lack of phase
25
Compressor malfunction
26
Low pressure protection of 311
27
Fan current protection
28
Fan lack of phase
29
Fan zero speed protection
30
PFC module protection
31
High pressure protection of 311
32
Zero speed malfunction
33
PWM malfunction
34
MCE malfunction
35
Compressor overcurrent protection
36
Compressor EE malfunction
37
Compressor start-up malfunction
38
311 fan speed has been malfunction
39
Low pressure protection
40
High pressure protection
41
PFC module malfunction
42
Shutdown stop
49
Electrical disconnect
50
DR stop
51
Summary of Contents for KOB30U-18HFN32
Page 1: ...i KAISAI SUPER DC INVERTER SERIES Service Manual 2019 ...
Page 12: ...Indoor Units 11 Service Space 3 Service Space 1000m m 1000mm 1000m m 1000m m ...
Page 15: ...Indoor Units 14 Wiring Diagrams ...
Page 20: ...Indoor Units 19 Air Velocity Distributions Reference Data 30 42K Cooling Heating ...
Page 21: ...Indoor Units 20 Air Velocity Distributions Reference Data 48 55K Cooling Heating ...
Page 26: ...Indoor Units 25 Field Wiring 10 Field Wiring KCD 24HRF32 KCD 36HRF32 ...
Page 27: ...Indoor Units 26 Field Wiring KCD 48HRF32 KCD 55HRF32 ...
Page 49: ...Indoor Units 48 Field Wiring 10 Field Wiring 18k 55k ...
Page 53: ...Indoor Units 52 Service Space 3 Service Space ...
Page 55: ...Indoor Units 54 Wiring Diagrams ...
Page 72: ...Indoor Units 71 Service Space 3 Service Space ...
Page 73: ...Indoor Units 72 Wiring Diagrams 4 Wiring Diagrams KCA3U 12HRF32X ...
Page 82: ...Outdoor Units Outdoor Units 82 10 Field Wiring KCA3U 12HRF32X ...
Page 87: ...Outdoor Units 87 Wiring Diagrams 3 Wiring Diagrams KOB30 12HFN32X ...
Page 88: ...Outdoor Units 88 Wiring Diagrams KOB30U 18HFN32 ...
Page 89: ...Outdoor Units 89 Wiring Diagrams KOCA30U 24HFN32 ...
Page 90: ...Outdoor Units 90 Wiring Diagrams ...
Page 91: ...Outdoor Units 91 Wiring Diagrams KOD30U 36HFN32 ...
Page 92: ...Outdoor Units 92 Wiring Diagrams ...
Page 93: ...Outdoor Units 93 Wiring Diagrams KOE30U 48HFN32 KOE30U 55HFN32 ...
Page 118: ...Installation 119 Refrigerant pipe installation ...
Page 183: ...Controller Electrical Control System 184 ...
Page 184: ...Controller Electrical Control System 185 ...