Electrical Control System
148
Troubleshooting
Is there any leakage, especially
in connective components such
as the gas valve and the liquid
valve?
No
Yes
Repair the leakage and
recharge the refrigerant
Replace indoor PCB
2.4.1.6. Refrigerant Leakage Detection
Malfunction conditions
Define the evaporator coil temperature T2 of the compressor starts
running as Tcool.
If the following occurs 3 times, the display shows "EC" and the unit
switches off:
In the first 8 minutes after the compressor starts up, if T2
<
Tcool
-
2
℃
is
not maintained for 4 seconds and compressor running frequency is not
higher than 50Hz for 3 minutes
Potential causes
●
T2 sensor error
●
Indoor PCB error
●
Refrigerant system error, such as leakage or blockages
Yes
Yes
No
Yes
Yes
Shut off the power supply and
turn it on
2 minutes
later. Is it
still displaying the error code?
Is there cool air blowing
out from indoor air outlet?
Are there any blockages in areas such as
the capillary or the welded points of the
pipes?
Clear the
blockages
Check if T2 sensor is well
fixed. Correct the installation
or replace T2 sensor. Does
the problem still remain?
Summary of Contents for KOB30U-18HFN32
Page 1: ...i KAISAI SUPER DC INVERTER SERIES Service Manual 2019 ...
Page 12: ...Indoor Units 11 Service Space 3 Service Space 1000m m 1000mm 1000m m 1000m m ...
Page 15: ...Indoor Units 14 Wiring Diagrams ...
Page 20: ...Indoor Units 19 Air Velocity Distributions Reference Data 30 42K Cooling Heating ...
Page 21: ...Indoor Units 20 Air Velocity Distributions Reference Data 48 55K Cooling Heating ...
Page 26: ...Indoor Units 25 Field Wiring 10 Field Wiring KCD 24HRF32 KCD 36HRF32 ...
Page 27: ...Indoor Units 26 Field Wiring KCD 48HRF32 KCD 55HRF32 ...
Page 49: ...Indoor Units 48 Field Wiring 10 Field Wiring 18k 55k ...
Page 53: ...Indoor Units 52 Service Space 3 Service Space ...
Page 55: ...Indoor Units 54 Wiring Diagrams ...
Page 72: ...Indoor Units 71 Service Space 3 Service Space ...
Page 73: ...Indoor Units 72 Wiring Diagrams 4 Wiring Diagrams KCA3U 12HRF32X ...
Page 82: ...Outdoor Units Outdoor Units 82 10 Field Wiring KCA3U 12HRF32X ...
Page 87: ...Outdoor Units 87 Wiring Diagrams 3 Wiring Diagrams KOB30 12HFN32X ...
Page 88: ...Outdoor Units 88 Wiring Diagrams KOB30U 18HFN32 ...
Page 89: ...Outdoor Units 89 Wiring Diagrams KOCA30U 24HFN32 ...
Page 90: ...Outdoor Units 90 Wiring Diagrams ...
Page 91: ...Outdoor Units 91 Wiring Diagrams KOD30U 36HFN32 ...
Page 92: ...Outdoor Units 92 Wiring Diagrams ...
Page 93: ...Outdoor Units 93 Wiring Diagrams KOE30U 48HFN32 KOE30U 55HFN32 ...
Page 118: ...Installation 119 Refrigerant pipe installation ...
Page 183: ...Controller Electrical Control System 184 ...
Page 184: ...Controller Electrical Control System 185 ...