17
8.5 Application 5
The wiring of room thermostat 5A(for fan coil units) and 5B(for floor eating loops) should follow 'method C' as described
in
9.7.6 Connection for other components/For room thermostat
, and the thermostat which connect to port 'C' (in the
outdoor unit) should be placed on the zone where floor heating loops is installed(zone B), the other one connect to port
'H' should be placed on the zone where fan coil units are installed(zone A).
NOTE
Dual setpoint function application with two room thermostat connect to the outdoor unit.
Space heating with two room thermostat application through floor heating loops and fan coil units. The floor heating loops
and fan coil units require different operating water temperatures.
The floor heating loops require a lower water temperature in heating mode compared to fan coil units. To achieve these two
set points, a mixing station is used to adapt the water temperature according to requirements of the floor heating loops. The
fan coil units are directly connected to the unit water circuit and the floor heating loops are after the mixing station. The
mixing station is controlled by the unit (or field supply, controls itself).
The operation and configuration of the field water circuit is the responsibility of the installer.
We only offer a dual set point control function. This function allows two set points to be generated. Depending on the required
water temperature (floor heating loops and/or fan coil units are required) . More details refer to
10.7 field setting /ROOM
THERMOSTAT
.
Make sure to correctly configure FOR SERVICEMAN in the user interface. Refer to
10.7 Field settings/Other heating
source
.
NOTE
Ensure that return water to the heat exchanger does not exceed 60°C. Never put the target water flow temperature set
point on the user interface above 60°C.
Make sure that the non-return valves (field supply) are correctly installed in the system.
The supplier will not be held liable for any damage resulting from failure to observe this rule.
CAUTION
During heating operation of the unit, the unit will operate to achieve the target water flow temperature set on the user
interface. When weather dependent operation is active, the water temperature is determined automatically depending on the
outdoor temperature.
During heating operation of the boiler, the boiler will operate to achieve the target water flow temperature set on the user
interface.
Never set the target water flow temperature set point on the user interface above (60°C).
2 3
6 7
8.1
8.2
8
10
9
11
11
FHL1
FHL2
FHLn
FCUn
FCU2
FCU1
17
T
T
4
5B
5A
23.1
23
23.2
24
A
B
1
1.5
1.4
1.2
1.3
1.7
1.6
1.1
18
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
2
3
Assembly unit
Assembly unit
Coding
Coding
4
6
Outdoor unit
Manometer
Pressure relief valve
Expansion vessel
Plate heat exchanger
Air purge valve
Flow switch
P_i: Circulation pump in the unit
Y-shape filter
Stop valve (field supply)
Wired controller
Drain valve (field supply)
7
8
8.1
8.2
9
10
11
17
23
23.1
FCU 1...n
Fill valve (field supply)
Balance tank (field supply)
Air purge valve
Drain valve
Expansion vessel (field supply)
P_o: Outside circulation pump (field supply)
Collector / distributor
(field supply)
FHL 1…n
5B
Room thermostat for zone 2
(field supply)
Floor heating loop (field supply)
Bypass valve (field supply)
Mixing station (field supply)
P_c: zone 2 pump (field supply)
Fan coil units (field supply)
23.2
SV3: 3-way valve (field supply)
24
Tw2: Zone 2 water flow temp. (individual purchase)
NOTE
The volume of balance tank(8) should be greater than 40L. The drain valve (6) should be installed at the lowest
positon of the system. Pump(10) and pump(23.1) should be controlled by outdoor unit and connect to corresponding
port in the outdoor unit(refer to
9.7.6 Connection for other components/For outside circulation pump P_o and
For tank loop pump P_d and mix pump P_c
).
The advantage of the dual set point control is that the heat pump will/can operate at the lowest required water flow
temperature when only floor heating is required. Higher water flow temperatures are only required in case fan coil
units are operating. This results in better heat pump performance.
Pump operation and space heating
The pump (1.7) and (10) will operate when there is request for heating from A and / or B. Pump (23.1) will operate only when
there is request for heating from B. The outdoor unit will start operating to achieve the target water flow temperature. The target
water leaving temperature depends on which room thermostat is requesting heating.
When the room temperature of both zones is above the thermostat set point, the outdoor unit and pump will stop operating.
5A
Room thermostat for zone 1
(field supply)
NOTE
Make sure to correctly configure the room thermostat installation on the user interface. Refer to "
10.7 Field
settings/ROOM THERMOSTAT
".
It is the installers’ responsibility to ensure that no unwanted situations can occur (e.g. extremely high temperature
water going towards floor heating loops, etc.)
The supplier does not offer any type of mixing station. Dual set point control only provides the possibility to use two
set points.
When only zone A requests heating, zone B will be fed with water at a temperature equal to the first set point. This
can lead to unwanted heating in zone B.
When only zone B requests heating, the mixing station will be fed with water at a temperature equal to the second
set point.Depending on the control of the mixing station, the floor heating loop can still receive water at a tempera-
ture equal to the set point of the mixing station.
Be aware that the actual water temperature through the floor heating loops depends on the control and setting of
the mixing station.
8.6 Application 6
Dual setpoint function application without room thermostat connect to the outdoor unit.
Heating is provided through floor heating loops and fan coil units. The floor heating loops and fan coil units require different
operating water temperatures.
The floor heating loops require a lower water temperature in heating mode compared to fan coil units. To achieve these two
set points, a mixing station is used to adapt the water temperature according to requirements of the floor heating loops. The
fan coil units are directly connected to the unit water circuit and the floor heating loops are after the mixing station. The
mixing station is controlled by the unit (or buy from the market, controlled by itself).
101
100
Summary of Contents for MONO KHC-22RX3
Page 1: ...INSTRUKCJA INSTALACYJNA INSTALATIONMANUAL POMPA CIEPŁA MONO MONO TYPE HEAT PUMP PL EN ...
Page 2: ......
Page 79: ...79 ...
Page 80: ......
Page 157: ...NOTE 157 ...
Page 158: ...NOTE ...
Page 159: ...16125300002403 V C ...
Page 160: ...kaisai com ...