18
8. Parameters
Model
KHX-14PY3
KHX-16PY3
Power Supply
/
380~415V/3N~/50Hz
380~415V/3N~/50Hz
Moisture Resistance
IPX
IPX4
IPX4
Electrical Shockproof
I
I
I
Heating Condition - Ambient Temp. (DB/WB): 7/6°C, Water Temp. (In/Out): 30/35°C
Heating Capacity Range
kW
5.40~14.95
8.00~22.00
Heating Power Input
Range
kW
1.05~3.85
1.60~6.90
Heating Current Input
Range
A
1.9~6.8
2.8~12.2
Cooling Condition - Ambient Temp. (DB/WB): 35/24°C, Water Temp. (In/Out): 12/7°C
Cooling Capacity Range
kW
3.60~10.50
4.20~15.00
Cooling Power Input
Range
kW
1.12~4.47
1.80~7.30
Heating Current Input
Range
A
2.0~7.9
3.2~12.9
Hot Water Condition - Ambient Temp. (DB/WB): 20/15°C, Water Temp. (In/Out): 15/55°C
Hot Water Capacity
Range
kW
6.50~18.50
10.00~27.00
Hot Water Power Input
Range
kW
1.27~4.65
1.90~7.10
Hot Water Current Input
Range
A
2.4~8.21
3.4~12.5
Max. Power Input
kW
5.3
9
Max. Current Input
A
10.5
15.8
Water Flow
m
3
/h
1.7
2.9
Refrigerant / Proper Input
kg
R290 / 0.85kg
R290 / 1.30kg
CO
2
Equivalent
Ton
0.0026
0.0039
Sound Pressure (1m)
dB(A)
44
47
Sound Power Level
(EN12102)
dB
58
62
Net Weight
kg
160
202
Operation Pressure(Low
Side)
MPa
0.8
0.8
Operation Pressure(High
Side)
MPa
3.0
3.0
Unit Dimension(L/W/H)
mm
1287×458×928
1250×540×1330
Shipping
mm
1420×540×1080
1380×570×1480
Summary of Contents for R290 Series
Page 1: ...INSTALLATIONMANUAL AIR TO WATER HEAT PUMP SERIES R290...
Page 2: ...MODEL KHX 14PY3 KHX 16PY3 Air to Water Heat Pump Installation Manual...
Page 9: ...6 4 Unit Dimension mm 4 1 Models KHX 14PY3...
Page 23: ...9 1 Model KHX 14PY3 9 Wiring Diagram 20...
Page 24: ...21 9 2 Model KHX 16PY3...
Page 38: ...35 V202109HH01...
Page 39: ...NOTE...
Page 40: ...kaisai com 20220425 0003...