LFIS-B-1211
Troubleshooting
Electrical Control System
99
2.4.4.3
.
E2 malfunction (Only for 12k)
Yes
Yes
Measure Vs, is it moving alternately
between positive value and negative
value?
(Vs is the voltage between S and N of
outdoor unit.)
Yes
Power off, then turn on the unit 5 seconds
later(reconnect the power wire).Is the error
still displaying after several minutes?
No
Yes
Change the outdoor main PCB.
Power on. Is the error extinguished?
Check all the wirings between indoor and
outdoor, indoor main PCB and outdoor main
PCB following the wiring diagram. Are all
the wirings connected correctly?
Is the wiring to the indoor main
PCB connected correctly?
Change the indoor main PCB.
Yes
Change the outdoor main PCB.
No
Is the wiring to the outdoor m a i n
PCB connected correctly?
Power on. Is the error extinguished?
Change the indoor main PCB.
No
Summary of Contents for SUPER DC INVERTER SERIES
Page 1: ...Contents i New Energy Requirement SUPER DC INVERTER SERIES Service Manual 2012 LFIS B 1211 ...
Page 2: ...ii General Information ...
Page 4: ......
Page 17: ...LFIS B 1211 Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Page 23: ...LFIS B 1211 Field Wiring Indoor Units 19 9 Field Wiring ...
Page 36: ...Duct Type LFIS B 1211 32 Indoor Units 10 Field Wiring ...
Page 40: ...Duct Type LFIS B 1211 36 Indoor Units 3 Service Space ...
Page 44: ...Field Wiring LFIS B 1211 40 Part 3 9 Field Wiring ...
Page 50: ...Wiring Diagrams LFIS B 1211 46 Part 3 KOU 36HFN1 RRC4 ...
Page 100: ...Troubleshooting LFIS B 1211 96 Electrical Control System 2 4 2 3 Up down panel is not closed ...