Troubleshooting
LFIS-B-1211
100
Electrical Control System
2.4.4.4
.
E2 malfunction (For 18-60k)
No
Power off, then turn on the unit 5
seconds later(reconnect the
power wire).Is the error still
displaying after several minutes?
Check whether the signal wire is
shield cable or whether the shield
cable is earthing?
Adopt shield cable/Shield
cable earthing.
Check whether the wire is correct
polarity? P to P, Q to Q, E to E?
No
Yes
Correct the connection.
No
Check if there’s any interference.
Such as too many lamps, power
transformers? Or the signal wire is
too long?
Yes
Remove interference.
Increase the capacity of anti-
interference
Yes
Check whether the signal wire is
broken?
Yes
Replace the signal wire.
Yes
Check whether the signal wires
insert on main PCB well?
Pull out and insert back.
No
No
Replace indoor m a i n PCB, is the
error distinguished?
Yes
Replace the outdoor main PCB.
No
Summary of Contents for SUPER DC INVERTER SERIES
Page 1: ...Contents i New Energy Requirement SUPER DC INVERTER SERIES Service Manual 2012 LFIS B 1211 ...
Page 2: ...ii General Information ...
Page 4: ......
Page 17: ...LFIS B 1211 Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Page 23: ...LFIS B 1211 Field Wiring Indoor Units 19 9 Field Wiring ...
Page 36: ...Duct Type LFIS B 1211 32 Indoor Units 10 Field Wiring ...
Page 40: ...Duct Type LFIS B 1211 36 Indoor Units 3 Service Space ...
Page 44: ...Field Wiring LFIS B 1211 40 Part 3 9 Field Wiring ...
Page 50: ...Wiring Diagrams LFIS B 1211 46 Part 3 KOU 36HFN1 RRC4 ...
Page 100: ...Troubleshooting LFIS B 1211 96 Electrical Control System 2 4 2 3 Up down panel is not closed ...