LFIS-B-1211
Troubleshooting
Electrical Control System
109
2.4.4.13. P3 malfunction
P3 display
Current protection of compressor
Judge 1: Check whether the
input current of the power
supply wire is more than
20A (For 36K & 48K with 1
phase, it is 30A)
Yes
Replace the electric control box
Check whether
the refrigerant
system is ok
Judge 2: Check whether the
outdoor ambient
temperature is higher than
50
℃
No
Stop the unit
Yes
Judge 3: Check whether the
outdoor unit is bad ventilation
No
Make the outdoor unit ventilate well
Yes
Judge 5: The refrigerant
pipe is blocked
No
Let the refrigerant out, then use the high
pressure nitrogen or refrigerant to blow pipe,
vacuumize and charge the refrigerant again
Yes
Judge 4: Check whether the
heat exchanger is dirty
No
Clean the heat exchanger
Yes
Yes
Replace outdoor main
board,and check whether
the system can run normally
No
Yes
Trouble is solved
Summary of Contents for SUPER DC INVERTER SERIES
Page 1: ...Contents i New Energy Requirement SUPER DC INVERTER SERIES Service Manual 2012 LFIS B 1211 ...
Page 2: ...ii General Information ...
Page 4: ......
Page 17: ...LFIS B 1211 Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Page 23: ...LFIS B 1211 Field Wiring Indoor Units 19 9 Field Wiring ...
Page 36: ...Duct Type LFIS B 1211 32 Indoor Units 10 Field Wiring ...
Page 40: ...Duct Type LFIS B 1211 36 Indoor Units 3 Service Space ...
Page 44: ...Field Wiring LFIS B 1211 40 Part 3 9 Field Wiring ...
Page 50: ...Wiring Diagrams LFIS B 1211 46 Part 3 KOU 36HFN1 RRC4 ...
Page 100: ...Troubleshooting LFIS B 1211 96 Electrical Control System 2 4 2 3 Up down panel is not closed ...