The Specification of Power
LFIS-B-1211
18
Indoor Units
8. The Specification of Power
Model
18000-24000Btu/h
36000
36000 Btu/h
INDOOR UNIT POWER
Phase
1-phase
1-phase
1-phase
Frequency and Voltage
220-240V, 50Hz
220-240V, 50Hz
220-240V, 50Hz
POWER WIRING (mm
2
)
3×1.0
3×1.0
3×1.0
CIRCUIT BREAKER (A)
15
15
15
OUTDOOR UNIT POWER
Phase
1-phase
1-phase
3-phase
Frequency and Voltage
220-240V, 50Hz
220-240V, 50Hz
380-420V, 50Hz
POWER WIRING (mm
2
)
3×2.5
3×4.0
5×2.5
CIRCUIT BREAKER (A)
30
40
30
Indoor/Outdoor Connecting Wiring
(Weak Electric Signal) (mm
2
)
3×0.5
3×0.5
3×0.5
Indoor/Outdoor Connecting Wiring
(Strong Electric Signal) (mm
2
)