LFIS-B-1211
Duct Type
Indoor Units
39
7. Accessories
Remote controller & Its
holder
1. Remote controller
1
2. Remote controller holder
1
3. Mounting screw (ST2.9×10-C-H)
2
4. Alkaline dry batteries (AM4)
2
Others
5. Owner's manual
1
6. Installation manual
1
7. Remote controller manual
1
8. The Specification of Power
Model
18000-24000Btu/h
36000
36000 Btu/h
INDOOR UNIT POWER
Phase
1-phase
1-phase
1-phase
Frequency and Voltage
220-240V, 50Hz
220-240V, 50Hz
220-240V, 50Hz
POWER WIRING (mm
2
)
3×1.0
3×1.0
3×1.0
CIRCUIT BREAKER (A)
15
15
15
OUTDOOR UNIT POWER
Phase
1-phase
1-phase
3-phase
Frequency and Voltage
220-240V, 50Hz
220-240V, 50Hz
380-420V, 50Hz
POWER WIRING (mm
2
)
3×2.5
3×4.0
5×2.5
CIRCUIT BREAKER (A)
30
40
30
Indoor/Outdoor Connecting Wiring
(Weak Electric Signal) (mm
2
)
3×0.5
3×0.5
3×0.5
Indoor/Outdoor Connecting Wiring
(Strong Electric Signal) (mm
2
)
Summary of Contents for SUPER DC INVERTER SERIES
Page 1: ...Contents i New Energy Requirement SUPER DC INVERTER SERIES Service Manual 2012 LFIS B 1211 ...
Page 2: ...ii General Information ...
Page 4: ......
Page 17: ...LFIS B 1211 Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Page 23: ...LFIS B 1211 Field Wiring Indoor Units 19 9 Field Wiring ...
Page 36: ...Duct Type LFIS B 1211 32 Indoor Units 10 Field Wiring ...
Page 40: ...Duct Type LFIS B 1211 36 Indoor Units 3 Service Space ...
Page 44: ...Field Wiring LFIS B 1211 40 Part 3 9 Field Wiring ...
Page 50: ...Wiring Diagrams LFIS B 1211 46 Part 3 KOU 36HFN1 RRC4 ...
Page 100: ...Troubleshooting LFIS B 1211 96 Electrical Control System 2 4 2 3 Up down panel is not closed ...