LFIS-B-1211
Electrical Control Function
Electrical Control System
83
T4
3℃
Time1
Time2
Time conditions:
time1
Time conditions(Meet the following conditions)
1.Running in heating mode
2. T4
≥3
℃
3. Compressor is on
4. T3
≤TempEnterDefrost_ADD
℃
Cleared conditions (Meet any one of the following conditions)
1. Compressor is off.
2. T3
>
TempEnterDefrost_ADD
℃
Time2
Time conditions(Meet the following conditions)
1.Running in heating mode
2. T4<3
℃
3. Compressor is on
4. T3
≤TempEnterDefrost_ADD
℃
Cleared conditions (Meet any one of the following conditions)
1. Compressor is off and T3
>
TempEnterDefro2
℃
last fo
r 20 minutes
2. Running in cooling mode.
3. Compressor is off for 1 hour.
Condition of entry defrosting:
time1+ time2
≥40 minutes, When defrosting is end,time1 and time2 are cleared.
Defrosting action
: