LFIS-B-1211
Troubleshooting
Electrical Control System
91
2.4.1.2. Outdoor unit malfunction
Whether the outdoor
main board has error
display
Refer to corresponding solving steps
Yes
No
No
Check whether the power is on
Replace outdoor main
board
Yes
Whether the outdoor
unit is power on
Check whether the
communication wire
between the indoor and
outdoor unit is
connected correctly
Yes
Connect the wiring well or
replace the communication wire
No
Replace the indoor PCB
Trouble is solved
check if the errors
happen again?
Yes
No
Outdoor unit malfunction