Troubleshooting
LFIS-B-1211
94
Electrical Control System
Control chip is in main PCB
NO.
1
2
3
4
5
Color
Orange
Grey
White
Pink
Black
Signal
Hu
Hv
Hw
Vcc
GND
Color
Red
Blue
Yellow
Signal
W
V
U
1) Release the UVW connector. Measure the resistance of U-V, U-W, V-W. If the resistance is not equal to each other, the fan
motor must have problems and need to be replaced. Otherwise, go to step 2.
2) Power on and when the unit is in standby, measure the voltage of pin4-5 in feedback signal connector. If the value is not 5V,
change the PCB. Otherwise, go to step 3.
3) Rotate the fan by hand, measure the voltage of pin1-5, pin 2-5 and pin 3-5 in feedback signal connector. If any voltage is
not positive voltage fluctuation, the fan motor must have problems and need to be replaced.
2.4.1.6.
Inverter compressor drive protection (Only for compact cassette 12k & console 12k)
Refer to the outdoor unit P6 malfunction part to solve this problem.
Summary of Contents for SUPER DC INVERTER SERIES
Page 1: ...Contents i New Energy Requirement SUPER DC INVERTER SERIES Service Manual 2012 LFIS B 1211 ...
Page 2: ...ii General Information ...
Page 4: ......
Page 17: ...LFIS B 1211 Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Page 23: ...LFIS B 1211 Field Wiring Indoor Units 19 9 Field Wiring ...
Page 36: ...Duct Type LFIS B 1211 32 Indoor Units 10 Field Wiring ...
Page 40: ...Duct Type LFIS B 1211 36 Indoor Units 3 Service Space ...
Page 44: ...Field Wiring LFIS B 1211 40 Part 3 9 Field Wiring ...
Page 50: ...Wiring Diagrams LFIS B 1211 46 Part 3 KOU 36HFN1 RRC4 ...
Page 100: ...Troubleshooting LFIS B 1211 96 Electrical Control System 2 4 2 3 Up down panel is not closed ...