KRSL series
Page
26
5.2.2 User menu
Press MENU Press USER PARA
Enter the User password, press Enter and Confirm.
MENU
DEFAULT
VALUE
FUNCTION
Load Pressure
(MPa/PSI)
00.65/94.30 Load Pressure
Unload Pressure
(MPa/PSI)
00.80/116.00 Unload Pressure
Fan Start T
(˚C/˚F)
0080/176
Fan will start if Discharge Temperature is above this
setting
Fan Stop T
(˚C/˚F)
0070/158
Fan will stop if Discharge Temperature is below this
setting
Motor Start Delay
(S)
0008
Set to bypass Motor Overload protection on start up, the
value here must be longer than the STAR DELAY TIME
plus LOAD DELAY TIME
Fan Start Delay
(S)
0003
Set to bypass Fan Motor Overload protection on start up
Star Delay
(S)
0006
Star Delta changeover time
Load Delay
(S)
0002
Delay to load after start running in Delta