Connecting without convection hood.
Place the grids or other openings in the surround for the
ventilation of a fireplace without convection hood. The grids
or opening protect the surround against high temperatures.
Ventilation grids must have a dimension of at least 350 cm² per
side. Grids can be replaced by opening with an intake of at least
350 cm² and an outflow of at least 350 cm².
TIP: Deviating connections can be submitted to Kalfire for
written approval.
Fig. 16: Surround without convection hood
(1) Air intake grid (two openings of at least 175 cm²)
(2) Grid for exit of convection air (two openings of at least 175 cm²)
Connecting with convection hood
The convection hood is mounted on the appliance in the factory
and so cannot be installed afterwards. The convection hood
ensures a delivery of controlled heat in the room where the gas
fire has been installed. This optimises the heat output of the
appliance.
Mount two aluminium ducts of (Ø 150 mm) to the convection
hood and connect these to the ventilation openings or grids
mounted on the convection hood. The total cross-section of the
outlets must be a minimum of 350 cm².
CAREFUL! Sealing the fireplace is at your own risk, damage
to the varnish caused by sealing falls outside of the factory
warranty.
1
2
1
2
1
2
1
2
Fig. 17: Surround with convection hood
(1) Air intake grid (two openings of at least 175 cm²)
(2) Grid for exit of convection air (two openings of at least 175 cm²)
19
Summary of Contents for G Series
Page 1: ...Installation instructions BALANCED FLUE GAS FIRES DON T COMPROMISE EN...
Page 2: ......
Page 4: ...4...
Page 43: ...1 4 6 7 5 2 3 43...
Page 45: ...1 3 2 5 4 6 7 8 8 7 45...
Page 47: ...1 9 4 7 3 8 5 6 2 10 47...
Page 49: ...5 1 2 3 7 4 6 8 10 9 9 49...
Page 51: ...4 5 3 6 1 1 51...
Page 52: ...7 2 7 7 2 2 8 52...
Page 54: ...4 5 2 1 1 3 54...
Page 55: ...9 8 6 7 1 55...
Page 57: ...5 6 7 8 3 2 2 1 57...
Page 58: ...9 4 4 8 58...
Page 60: ...5 2 9 6 2 1 4 3 60...
Page 61: ...7 7 10 11 8 61...
Page 63: ...1 7 7 3 4 6 2 7 63...
Page 64: ...2 4 4 5 5 8 64...
Page 66: ...7 4 5 6 1 8 9 66...
Page 67: ...3 3 11 2 10 10 12 67...
Page 69: ...1 2 6 6 8 8 9 7 7 4 With gas type G30 log 4 to be placed at extreme right 3 4 5 11 69...
Page 72: ...10 2 1 9 11 3 3 4 5 5 7 6 72...
Page 73: ...13 12 12 12 8 73...
Page 76: ...3 1 6 5 4 2 13 76...
Page 77: ...14 7 10 11 8 12 12 Other side Divide 15 cryptonite and 16 ash 77...
Page 80: ...3 4 5 7 1 3 4 5 6 1 4 5 1 3 4 1 3 2 1 2 3 1 3 1 2 4 5 1 6 2 6 7 14 12 11 11 3 80...
Page 81: ...3 4 5 7 8 1 3 4 7 9 10 8 3 4 5 6 7 8 1 3 4 5 6 7 8 1 3 4 5 6 7 1 9 10 8 15 13 81...
Page 84: ...4 3 5 2 3 4 5 1 2 3 4 5 1 1 2 3 4 1 1 2 1 1 1 2 1 1 1 1 1 2 3 4 5 6 6 1 1 1 14 11 84...
Page 94: ...94...
Page 95: ...95...
Page 96: ...Gelo rveldweg 21 5951 DH Belfeld info kalfire nl KALFIRE COM DON T COMPROMISE REF V01 2019 EN...