Installation
ProLine 2200 User’s Manual REV N
This information is subject to the controls of the Export Administration Regulations [EAR]. This information shall not be provided to
non-U.S. persons or transferred by any means to any location outside the United States contrary to the requirements of the EAR.
3-4
3 Phase
Input Voltage
(VAC)
Input Current
at Maximum Output
(amps)
Recommended
Time-Delay Fuse Size
(amps)
208V 60Hz
115
170
230V 60Hz
104
150
380V 50/60Hz
63
90
415V 50/60Hz
58
80
460V 60Hz
52
75
575V 60Hz
42
60
Use a Type SO power cable to connect the primary power to the ProLine power supply.
The power cable should have a 600 volt minimum rating and should be sized according
to local and national codes. Route the power cable through the lower strain relief on the
rear of the power supply and connect it to the input terminal block TB5 as shown in
Figure 3-2. TB5 is located on the base of the power supply behind the left side cover.
Be
sure to connect the primary ground cable to the ground stud on the input terminal
block
.
L1
L2
L3
GND
Figure 3-2 Primary Power Connections