135
EN
PROBLEM
POSSIBLE CAUSE
REMEDY
No increase in
temperature with
Hydro Insert in
operation
1. Incorrect combustion
adjustment
2. Hydro Insert/system dirty
3. Insufficient Hydro Insert power
1. Check parameters
2. Check and clear the Hydro Insert
3. Check that the Hydro Insert is properly sized for
the requirements of the system
Anomalies related to the plumbing circuit
Condensation
in Hydro Insert
1. Incorrect setting maximum
water temperature in the Hydro
Insert
2. Insufficient fuel consumtion
1. Set the Hydro Insert to a higher temperature. The
maximum water temperature in the Hydro Insert is
65 ° C and can not be set below 40 ° C or above 80
° C. It is advisable to never adjust the temperature
below 50/55 ° C to avoid condensation in the Hydro
Insert.
Adjust the power of the pump at a higher
temperature to 50/55 ° C.
2. Contact your Authorized Assistance Center
Radiators cold in
winter but the Hydro
Insert boils
1. Circulator does not run
because blocked
2. Radiators have air in them
1. Free up the circulator by removing the plug and
turning the shaft with a screwdriver.
Check the electrical connections of the same,
replace if necessary
2. Vent the radiators
Hot water in not
provided
1. Circulator pump blocked
1. Free the circulator pump
The Hydro Insert boils
under “modulation”
that reaches the
temperature set on
the thermostat of the
Hydro Insert
1. It ‘been set to a value of
thermostat too high
2. It was set too much power to
the implant.
1. Lower the temperature in the Hydro Insert
2. Reduce the value of operating power
In the automatic
position the Hydro
Insert always runs at
full power
1. Room thermostat set to
maximum
2. Temperature sensor defective
3. Control panel defective or
broken
1. Reset the thermostat temperature
2. Check the operation of the sensor and replace
if necessary
3. Check the panel and replace if necessary
The Hydro Insert
starts up “alone”
1. Incorrect programming of the
cronothermostat
1. Check the settings of the cronothermostat
The power does not
change even if you
manually adjust
1. The board is set to automatic
correction of power in proportion
to the temperature
1. Contact your Authorized Assistance Center