10
could cause current leakage or electric shock.
CAUTION!
To allow for proper air flow, a minimum of fifteen centimeter of clearance
space is required behind the freezer.
5.2 Wiring
CAUTION!
Connect the equipment to the correct power source. Incorrect voltage can
result in severe damage to the equipment.
CAUTION!
For personal safety and trouble-free operation, the unit must be properly
grounded before it is used. Failure to ground the equipment may cause
personal injury or damage to the equipment. If the power supply outlet is not
grounded, it is necessary to install a ground from the ground screw located
on the lower right back side of the unit by qualified engineers.
Always connect the freezer to a dedicated (separate) circuit. Each freezer is equipped
with a service cord and plug designed to connect it to a power outlet which it delivers
the correct voltage. Supply voltage must within
+10%, -10%
of the freezer rated
voltage.
CAUTION!
Never cut the grounding prong from the service cord plug. If the prong is
removed, the freezer would not be properly grounded.
5.3 Leveling
The unit must be level both front to back and side to side.
To level chest models, leave the casters in place and shim the low wheel(s) with strips
of sheet metal cut wider than the caster.
Upright models have adjustable leveling feet which are located adjacent to the front
casters. Extend the leveling feet by rotating them counterclockwise to contact them to
the floor. Ensure the unit is level.