5.
Transportation and storage
Boilers are stored and transported fastened onto wooden pallet and twisted with
polythene film, if nothing else is agreed in the supply agreement.
Boilers are allowed to transport exclusively in vertical position with any kind of
covered transport. If weather is dry, open transport is allowed. Extra measures have to
be taken to protect boilers from falling down, scratching against each other. During
loading/unloading/transportation it is prohibited to beat, turn, throw the boilers.
Boilers are stored in dry premises, without presence of chemically active substance
gases.
Note. Product packing (wooden pallet and polythene film) disposal actions shall meet
the environmental requirements and rules of the user’s country. In the extreme
case wooden pallet can be used as fuel for the boiler.
Picture 2. Boiler packing for transportation
6.
Boiler installation
Boiler is to be installed in the premises meeting the relevant requirements of the
country where boiler has to be installed.
Boiler firing requires much air, therefore is necessary to ensure the sufficient fresh
air intake in the boiler operate premise.
Boiler is to be positioned upright or declined to front by no more than 1
o
. Premise
floor must be even, not flammable and capable to withstand the load up to 1,3 t/m².
It is recommended to install fume extraction hood above the boiler.
It is prohibited to install boiler in the living rooms or corridors.
Prior connecting the boiler to heating system and chimney, take into consideration
the fact that the boiler will has to be maintained (cleaned, adjusted etc.). Minimum
distances between the boiler and walls necessary for its maintenance and fire
precaution are shown in
picture 2
.