41
a
Position the sensor or simulated input so that it is
near the low scale point (e.g. 0 mils, 0 Volts, 4 mA)
push the "ENTER" button.
b
Use the "SET" button to change the value of the
flashing digit. When the flashing digit is correct,
push the enter button. The flashing digit will now
move to the next right hand digit. Continue until
all digits are correct with the rightmost digit still
flashing. (e.g. OOOO-- still flashing)
c
Push both "SET" and "ENTER" buttons at the same
time to program in this scale factor. In other
words, when the indicator receives a process input
signal identical to the simulated (calibration) one it
will display the same value shown now. (e.g. 4mA =
0000).
Note:
While the indicator is calibrating itself "oo" will appear in the
display. After a few seconds it will return to display "HI" (go to
step 4d) or "ERR" (see error message table).
d
with "HI displayed change the input to simulate
the +Full scale (High) (e.g. 20mA). Repeat steps as
shown in steps
a
,
b
, and
c
changing the digits to
represent the Full Scale desired display (e.g. 7500).
When complete the indicator will then go to the
decimal point position.
5)
with the decimal points displayed
a
push the "SET" button until desired position is
displayed.
b
Push "SET" and "ENTER" buttons at the same time
to program into memory.
10)
Return the "PROCESS/SCALING" dip switch to the PROCESS position. Replace
the front lens.
Summary of Contents for SERIES 8000
Page 2: ......
Page 9: ...9 fig 1 Full 19 Subrack Rear Front Outline Drawing...
Page 10: ...10 Fig 2 Full 19 Subrack Top View Outline Drawing...
Page 11: ...11 fig 3 Full 19 Subrack Rear Front with Display...
Page 12: ...12 fig 4 Full 19 Subrack Rear Front with Dual Display...
Page 14: ...14 fig 5 Rack with Display Outline Drawing...
Page 15: ...15 fig 6 Rack Outline Drawing...
Page 16: ...16 fig 7 Rack with Display Outline Drawing...
Page 28: ...28 fig 15 Back Plane Template...
Page 34: ...34 fig 20 Dual 1 8 DIN Mounting Panel 814873 002...