KaCool D HC
Assembly, installation and operating instructions
24
Connecting the condensate pump
Push the suction hose as far as it will go and fix in place with a cable tie to prevent the pump from running dry.
Connect the hose to the condensate drain (separate). Direction of flow: refer to the arrow on the side of the housing
Max. flow rate [l/h]
20 l/h
Max. suction height [m]
3 m
Max. delivery height [m]
10 m (flow rate = 4 l/h)
Max. pressure [m]
14 m (flow rate = 0 l/h)
Noise level at 1 m according to
EN ISO 3744 [dBA] (measured in the LNI laboratory, pump
operated with water, not installed)
20 dBA
Noise level when installed at 1 m [dBA] (measured in the Sauermann
acoustic laboratory, pump
operated with water)
≤27 dBA
Power supply
230 V 50/60 Hz – 14 W
Insulation class
(double insulated)
Switching points
ON: 16 mm, OFF: 11 mm, ALARM: 19 mm
Safety contact
NC 8 A ohmic load – 250 V
Overheating protection (switching-off point)
115 °C (auto-reset)
Operating mode
100 % ED - continuous operation
Protection class
IP20
Safety standards
CE & EAC
RoHS Directive
Compliance
Waste Electrical and Electronic Equipment Directive (WEEE)
Compliance (EAR registered)
Weight – Packaging dimensions
0.48 kg – L135 x W135 x H90 mm
Tab. 4: Technical data, condensate pump