KaCool D HC
Assembly, installation and operating instructions
27
Terminal assignment, KaCool D HC
F
1
UB
Gnd
E/T
Uc_M
Uc_P
PE PE
PE N
L
Ls N cp val
C P1 P2 AP
10V E/T Uc Gnd
Gnd
Uc
E/T
10V
P2
C
P1
C
val
N
NC
com
Ls
N
Ls
N
PE
PE
-N1
PE
N
L
V
a
l
C
P1
P2
AP
0
-1
0V
G
N
D
Mains power supply:
230 V AC / 50 Hz
Valve:
230 V Open/Closed
Evaluation:
- Filter message
- Condensate alarm
Control signal
0 - 10 V DC
Patch board
Note these points in the following layout plans for
KaCool D HC
:
Comply with the details on cable types and cabling with due consideration of VDE 0100.
Without *: NYM-J. The requisite number of wires, including PE conductor, is stated on the cable. Cross-sections are not
stated, as the cable length is involved in the calculation of the cross-section.
With *: J-Y(ST)Y 0.8mm. Lay separately from high voltage lines. If other types of cables are used, they must be at least
equivalent.
Type F is recommended when using RCCBs. Refer to the provisions of DIN VDE 0100 Parts 400 and 500 when designing
the rated fault current, and note the leakage currents.
Note the electrical data when designing the on-site mains power supply and fuse.