DIP Switch Factory Settings - 2-pipe System
DIP Switch Factory Settings - 4-pipe System
When using control configuration C2, all slave units must be fitted
with a clip-on temperature sensor.
Ka
Control
für Venkon
INSTALLATIONS- UND BEDIENUNGSANLEITUNG
1.48
Venkon
35
DIP
2-pipe
Functions
C1
C2
DIP1
OFF
OFF
Clip-on temperature sensor not fitted
DIP2
ON
ON
H/C changeover via digital input DI2
DIP3
OFF
OFF
Operating function lock disabled
DIP4
OFF
OFF
2-pipe system
DIP5
OFF
OFF
OFF must be set
DIP6
ON
OFF
OFF = Room control to clip-on temperature sensor
ON = Room control to sensor in the KaController
DIP
4-pipe
Functions
C1
C2
DIP1
OFF
OFF
Clip-on temperature sensor not fitted
DIP2
OFF
OFF
Digital input DI2 not operational
DIP3
OFF
OFF
Operating function lock disabled
DIP4
ON
ON
4-pipe system
DIP5
OFF
OFF
OFF must be set
DIP6
ON
OFF
OFF = Room control to clip-on temperature sensor
ON = Room control to sensor in the KaController
DIP switch 2-pipe system control
configuration C1
DIP switch 2-pipe system control
configuration C2
DIP switch 4-pipe system control
configuration C2
DIP switch 4-pipe system control
configuration C1