Control via 0 - 10 VDC
The 0 - 10 VDC control signal is interpreted for speed according to the following values:
Control signal
Function
0 V
Off
2 - 10 V
n
(2 V)
- 100%
The speed can be limited to approx. 50% of the maximum speed by the potentiometer in the junction box.
Observe these points in the following layout plans for TIP with electromechanical control (**00):
Comply with the details on cable types and cabling with due consideration of VDE 0100.
Without *: NYM-J. The requisite number of wires, including PE conductor, is stated on the cable. Cross-sections are not
stated, as the cable length is involved in the calculation of the cross-section.
With *: J-Y(ST)Y 0.8 mm, max. 100 m between the fan speed controller and the last unit heater; provide a shield on one
side when longer than 20 m. Lay separately from high voltage lines.
With **: Sensor connection cable 1.5 mm² e.g. J-Y(ST) Y, 4 x 2 x 0.8 mm, max. 100 m. Lay separately from high voltage
lines.
With ***: J-Y(ST)Y, 0.8 mm, max. 50 m. Lay separately from high voltage lines.
With ****: J-Y(ST)Y, 0.8 mm, max. 100 m. Lay separately from high voltage lines.
If other types of cables are used, they must be at least equivalent.
The terminals on the unit are suitable for a maximum wire cross-section of 2.5 mm², the mains plug for max. 4.0 mm².
All RCCBs used must be all current-sensitive (type B). Refer to the provisions of DIN VDE 0100 Parts 400 and 500 when
designing the rated fault current.
Note the electrical data when rating the in-situ mains power supply and fuse.