13
Ultra
1.54
Comfortable indoor climate in high-end interiors
Installation and operating instructions
Example showing suspended ceiling
• Use the drilling template to draw the four fixing
points on the solid ceiling and drill the holes.
• Tap the rawplugs into the holes. Screw in the
sufficiently long threaded rods using the M8
hexagonal nuts and washers as per the diagram.
Caution!
Never lift the unit by the louvres when
transporting or installing it.
• Lift the unit under the ceiling and attach it to the
brackets by pushing the slots on the brackets as
shown on the adjacent drawing onto the threaded
rods.
• Tighten the screw nuts and ensure that the Ultra is
level, particularly with cooling mode.
Use all four fixing points! Make sure that the gap
(approx. 6 mm) between the ceiling and the air intake
crown is not filled by subsequent work on the ceiling
, such as plastering, as it would then be impossible to
fit or remove the intake crown.
Installation with a solid ceiling
• Use the drilling template to draw the four fixing
points on the solid ceiling and drill the holes.
• Tap the rawlplugs into the holes and insert the M8
screws with washers and screw nuts as per the
diagram.
Caution!
Never lift the unit by the louvres when
transporting or installing it.
• Lift the unit under the ceiling and attach it to
the brackets by pushing the slots on the brackets
as shown on the adjacent drawing onto the M8
screws.
• Tighten the screws and ensure that the Ultra is
level, particularly with cooling mode.
Use all four fixing points!
Caution!
Make sure that
the gap between the ceiling and the air intake crown
is not filled by subsequent work on the ceiling, such
as plastering, as it would then be impossible to fit or
remove the air intake crown.
Refer to “Commissioning” on page 35 for adjustment of the louvre
position.
Exampling showing
suspended ceiling
Suggested
arrangement with
solid ceilings
Solid ceiling
Threaded rod
U-washer
M8 threaded rod
Suspended ceiling
M8 hexagonal nut
Excess thread
(ensure that the rod
is long enough!)
Solid ceiling
Rawlplug
U-washer
M8 screw
Bracket
Air intake crown
M8x16 tooth
locking screw
Anti-twist
mechanism
Ultra base plate
Air intake crown
Bracket
M8x16 tooth
locking screw
Anti-twist
mechanism
Ultra base plate
Louvre
x=> Maintain this gap in order to undertake any
service work on the intake crown!
x=> Maintain this gap in order to undertake any
service work on the intake crown!
Provided by the customer
Provided by the
customer
Scope of delivery
Scope of delivery
Louvre