16
1.54
Ultra
Comfortable indoor climate in high-end interiors
Installation and operating instructions
9. Installation of condensation drain (with Ultra for cooling)
9.1 Routing the condensation lines
Note the following when routing the condensation lines:
• Condensation collection lines should have an appropriately sized inner
diameter.
• Make sure that they are routed with a gradient towards a free outlet.
Please refer to the separate instructions for the condensation pump for
more information on maintenance, delivery height etc.
9.2 Connecting the condensation pump
Ultra units for cooling are fitted with a condensation tray to collect
condensation from the air drawn in. This is drawn off by the condensation
pump and discharged along a hose connected on the pressure side.
Depending on conditions on site, the water can be discharged into drainage
lines, possibly with a trap connection. A float switch monitors the water level
and switches the pump off if it is exceeded (refer to separate instructions).
The condensation is drained off. An alarm contact is triggered in the event
of a malfunction of the condensation drain.
9.2.1 Ultra without fitted KaControl module, recirculation air
We would recommend automatically terminating cooling operation when
the maximum condensation level is reached to prevent the condensation
tray from overflowing.
Wiring of condensation pump
Ultra cooling mode
Ultra fan motor
Cable with plug
Condensation pump
Float
switch
Terminal block
(external)
Mains power supply
to condensation pump
Alarm contact