17
Ultra
1.54
Comfortable indoor climate in high-end interiors
Installation and operating instructions
Wiring and fuses
The condensation pump needs a separate power supply 230 V/50 Hz.
Additional wires are needed (top image) to evaluate the alarm contact.
Line: NYM-J, 1.5 mm² or similar.
9.2.2 Ultra with fitted KaControl module, recirculation air
Voltage supply and alarm contact are factory-wired on the Ultra. In the
event of an alarm message, the KaControl system closes the valve and the
fan is switched to stage 1.
Ultra for cooling
(example shows axial fan)
Condensation pump
Connection of condensation pump
NC
C
PE
N
L
Cable with plug
black
grey
blue
brown
Condensation pump
Terminal block (external)
Mains power supply:
Voltage: 230 V/50 Hz
power consumption: 14 W
alarm contact:
Com and NC: Interruption of the power circuit as soon as the alarm
level in the float module is reached.
Voltage: max. 250 V
Switching current: max. 5 A