42
1.54
Ultra
Comfortable indoor climate in high-end interiors
Installation and operating instructions
Fault
Possible cause
Remedy
Fan does not rotate when
power is applied to the
module and control signal
< 1 V DC
Main fuse on the connecting PCB and/or fuse on
the power PCB is faulty
Check fuses
Thermal contact (risk of overheating) or
overheating protection in the module has triggered
Check motor or module temperature and allow to
cool down if necessary.
Clarify the cause of overheating (e.g. blocked motor,
impermissibly high power consumption, intake
temperature too high, dirty filter); switch unit off and
on again.
Fan does not rotate 100 % at
max. control signal 10 V DC
Overheating protection in module has reduced
speed
Check automatic speed increased after module has
cooled down
DIP switch for maximum limit incorrectly set
Check DIP switches
Fan rotates at fixed undefined
speed in spite of change to
control signal 0-10 V DC
Control voltage poles switched
Correctly connect control voltage
Fault
Possible cause
Remedy
Fan does not rotate when
power is applied to the
module and control signal
> 4 V DC
Main fuse on the connecting PCB, secondary fuse
on the connecting PCB, fuse on the power PCB
and/or fuse on the KathermBoard is faulty
Check fuses
Control voltage poles switched
Correctly connect control voltage
Thermal contact (risk of overheating) or
overheating protection in the module has triggered
Check motor or module temperature and allow
to cool down if necessary. Clarify the cause of
overheating (e.g. blocked motor, impermissibly high
power consumption, intake temperature too high,
dirty filter); switch unit off and on again
Fan does not rotate 100 % at
max. control signal 10 V DC
Overheating protection in module has reduced
speed
Check automatic speed increase after module has
cooled down
DIP switch for maximum limit incorrectly set on
PCB
Check DIP switches
Potentiometer for maximum limit incorrectly set on
KathermBoard
Check potentiometer
14.3 AC single-phase motor with power module type ...16V
14.4 AC single-phase motor with KaControl recirculation air module type ...16C1
Refer also to flash code in chapter 10.3.2.2 Continuously variable power module
Refer also to flash code in chapter 10.3.2.2 Continuously variable power module
For other faults refer also to Assembly and Installation Instructions for KaControl for Unit Heaters I438.