Venkon XL
Beschreibung
Assembly, installation and operating instructions
63
Parameter
Function
Standard
Min.
Max.
Unit
Venkon XL
4
P035
Time that the fan runs on after change of operating mode
to stage 1
0
0
255
s
0
P036
Type of setpoint setting
0
0
1
-
0
P037
Display
1
0
7
-
1
P038
Lock/disable function on control unit
72
0
255
-
72
P039
Function of digital output V2 (in 2-pipe system)
0
0
3
-
0
P040
Valve actuation by means of pulse width modulation
0
0
1
-
0
P041
Reset time of PI controller to actuate the fan in automatic
fan mode
0
0
20
min
0
P042
Fan setting: lock and activate fan stages
0
0
127
-
0
P043
Function of digital input DI1
0
0
22
-
12
P044
Function of digital input DI2
0
0
22
-
0
P045
Threshold voltage for potentiometer, which switches on
unit
10
0
100
kOhm
10
P046
Temperature setting corresponds to minimum resistance
value = 10 kOhm in the potentiometer
18
12
34
°C
18
P047
Temperature setting corresponds to maximum resistance
value = 100 kOhm in the potentiometer
24
13
35
°C
24
P048
Threshold voltage for potentiometer for starting up fans
10
0
100
kOhm
10
P049
Threshold voltage for potentiometer for maximum fan
speed
90
0
100
kOhm
90
P050
Fan setting: max. fan speed
100
0
100
%
100
P051
Fan setting: min. fan speed
0
0
90
%
0
P052
Fan setting: speed limitation activated
0
0
1
-
0
P053
Valve actuation by pulse width modulation of valve switch-
ing cycle
15
10
30
min
15
P054
Configuration of bus system
0
0
2
-
0
P055
Display of heating/cooling symbols in automatic mode
0
0
1
-
1
P056
DI2 setting (polarity) when DIP 4 = ON
1
0
1
-
1
P057
Reset setpoint setting to the value of P01 (after changing
operating program)
0
0
1
-
0
P058
Sensor calibration: sensor AI1
0
-99
127
K/10
0
P059
Supply air temperature setpoint in heating mode
35
0
50
°C
35
P060
Supply air temperature setpoint in cooling mode
18
0
50
°C
18
P061
Sensor calibration: sensor in the KaController
0
-99
127
K/10
0
P062
Sensor calibration: sensor AI2
0
-99
127
K/10
0
P063
Outside temperature <P63 fan increase by P122
0
-99
127
°C
0
P064
Sensor calibration: sensor AI3
0
-99
127
K/10
0
P065
reserved
-
-
-
-
-
P066
Master/Slave assignment in CAN bus
0
0
1
-
0
P067
Serial CANbus address
1
1
125
-
1
P068
Logic of hydronic algorithms
0
0
7
-
0
P069
Network address
1
0
207
-
1
P070
Dependence of the hydronic algorithms (on Slaves)
0
0
7
-
0
P071
Serial address of Slave 1
0
0
207
-
0
P072
Serial address of Slave 2
0
0
207
-
0
P073
Serial address of Slave 3
0
0
207
-
0
P074
Serial address of Slave 4
0
0
207
-
0
Summary of Contents for Venkon XL
Page 2: ......
Page 5: ...5 13 2 ERP Datenblatt Venkon XL 70...
Page 67: ...Venkon XL Beschreibung Assembly installation and operating instructions 67 13 Certificates...
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ...www kampmanngroup com hvac products fan coils venkon xl 02 20 ENSAP Nr 1374732...