2.2
Limits of operation and use
Limits of operation
Min./max. water temperature
°C
4-90
Min./max. air intake temperature
°C
6--40
Min./max. air humidity
%
20-60
Min. operating pressure
bar/kPa
-
Max. operating pressure
bar/kPa
10/1000
Min./max. glycol percentage
%
0-50
Tab. 1: Limits of operation
Operating voltage
230 V/ 50/60 Hz
Power/Current consumption
On the type plate
Tab. 2: Operating voltage
We would refer to VDI-2035 Sheets 1 & 2, DIN EN 14336 and DIN EN 14868 with regard to the properties of the medium
used to protect the equipment. The following values provide further guidance.
The water used should be free of contamination, such as suspended substances and reactive substances.
Water quality
pH value (at 20 °C)
8-9
Conductivity (at 20 °C)
μS/cm
< 700
Oxygen content (O
2
)
mg/l
< 0.1
Hardness
°dH
4-8.5
Sulphur ions
not measurable
Sodium ions (Na
+
)
mg/l
< 100
Iron ions (Fe
2+
)
mg/l
< 0.1
Manganese ions (Mn
2+
)
mg/l
<0.05
Ammonia ions (NH
4+
)
mg/l
< 0.1
Chlorine ions (CI)
mg/l
< 100
CO
2
< 50
Sulfate ions (SO
4
2-
)
mg/l
< 50
Nitrite ions (NO
2-
)
mg/l
< 50
Nitrate ions (NO
3-
)
mg/l
< 50
Tab. 3: Water quality
Summary of Contents for Venkon XL
Page 2: ......
Page 5: ...5 13 2 ERP Datenblatt Venkon XL 70...
Page 67: ...Venkon XL Beschreibung Assembly installation and operating instructions 67 13 Certificates...
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ...www kampmanngroup com hvac products fan coils venkon xl 02 20 ENSAP Nr 1374732...