Venkon XL
Beschreibung
Assembly, installation and operating instructions
32
At the end of the work, attach all wire clamps (with conventional pliers) and check that they are sitting tightly. Check assign-
ment and positions against the following figure:
1
2
3
4
5
6
7
Fig. 32: Attaching the wire clamps
Position
Model [mm]
1
10.1
2
10.1
3
6.1
4
10.1
5
10.1
6
21.2
7
22.1
Tab. 8: Assignment of wire tightening clamps
Technical data on the condensation pump
Max. pumping quantity
20 l/h
Maximum suction height
3 m
Maximum delivery height
10 m
Power supply
230 V-50 Hz-14 W
Safety shut-down contact
NC 8A ohmic load
Overheating protection
115°C
Operating mode
Continuous operation
Protection class
IP20
Switching points (mm)
ON: 16, Off: 11, Alarm: 19
Noise level at a distance of 1 m
20 dBA
Tab. 9: Technical data for Sauermann SI30 condensation pump