Voltage Class
380 to 480 VAC
Model: GT600-4TxxxG(-L)
200
220
250
280
315
355
400
450
Frame size
T10
T11
T12
Dimension
(GT600-
4TxxxG)
Height
Width
Depth
[H1]: 1134 mm
[W]: 300 mm
[D]: 500 mm
[H1]: 1284 mm
[W]: 330 mm
[D]: 545 mm
[H1]: 1405 mm
[W]: 340 mm
[D]: 545 mm
Dimension
(GT600-4TxxxG-
L)
Height
Width
Depth
[H1]: 1472 mm
[W]: 300 mm
[D]: 500 mm
[H1]: 1622 mm
[W]: 330 mm
[D]: 545 mm
[H1]: 1733 mm
[W]: 340 mm
[D]: 545 mm
Mounting Hole (mm)
Φ13
Φ16
Dr
iv
e Inp
ut
Rated input voltage
Three-phase 380 to 480V, -15% to +10%
Rated input current [A]
365
410
441
495
565
617
687
782
Rated input frequency
50/60 Hz, ±5%
Power capacity, [kVA]
334
375
404
453
517
565
629
716
Dr
iv
e
O
utpu
t
Applicable motor
[kW]
200
220
250
280
315
355
400
450
[HP]
267
293
333
373
420
473
533
600
Output current, [A]
377
426
465
520
585
650
725
820
Default carrier frequency
[kHz]
3
3
3
3
3
3
3
3
Overload capacity
150% for 60 Sec
130% for
60 Sec
Output Voltage
Three phase 0 V to input voltage
Max. output frequency
50 to 500 Hz
B
rak
ing
Res
is
tor
Recommended power,
[kW]
38
42
48
54
60
69
78
87
Recommended
resistance,
[Ω]
2.9
2.7
2.3
2.1
1.9
1.7
1.5
1.3
T
hermal
Des
ign
Thermal design power,
[kW]
4.15
4.55
5.06
5.33
5.69
6.31
6.91
7.54
Air flow, [CFM]
638.4
722.5
789.4
882
645
860
860
860
Enclosure
IP00
1
Table 1-2 Ratings of
GT600-4T200G(-L) to GT600-4T450G(-L)
Summary of Contents for GT600-4T132G
Page 1: ...GT600 AC Drive...
Page 5: ......
Page 86: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 86 5 2 Setup Flowchart 87...
Page 87: ......
Page 100: ...5 Quick Setup 98 5...
Page 280: ...8 Peripherals and Options 278 8...
Page 306: ...12 303 11...
Page 362: ......