1. Product Information
- 18 -
1.5 De-rating
The drive can be operated at above rated ambient temperature, altitude and default carrier frequency by
de-rating drive capacity.
■
Carrier Frequency De-rating
When carrier frequency of the drive is increased above default setting, you need to de-rate rated
drive output current according to the following table:
Power
Carrier Frequency
Phd (kW)
3 kHz
4 kHz
5 kHz
6 kHz
7 kHz
8 kHz
18.5
100.0%
100.0%
100.0%
100.0%
95.7%
91.6%
22
100.0%
100.0%
100.0%
100.0%
95.5%
91.4%
30
100.0%
100.0%
100.0%
100.0%
93.5%
87.7%
37
100.0%
100.0%
100.0%
94.4%
89.0%
84.0%
45
100.0%
100.0%
100.0%
94.0%
88.6%
83.7%
55
100.0%
100.0%
94.1%
88.9%
84.0%
79.5%
75
100.0%
91.8%
84.2%
77.5%
70.9%
65.2%
90
100.0%
90.8%
82.3%
74.9%
-
-
110
100.0%
91.9%
84.4%
77.7%
-
-
132
100.0%
95.65%
91.30%
86.96%
-
-
160
100.0%
94.08%
88.16%
82.24%
-
-
200
100.0%
93.07%
86.15%
79.22%
-
-
220
100.0%
93.69%
87.38%
81.06%
-
-
250
100.0%
93.43%
86.86%
80.29%
-
-
280
100.0%
93.59%
87.18%
80.77%
-
-
315
100.0%
93.90%
87.81%
81.71%
-
-
355
100.0%
93.54%
87.08%
80.26%
-
-
400
100.0%
93.79%
87.59%
81.38%
-
-
■
Ambient Temperature De-rating
Drive operation between -10°C to 40°C is normal without de-rating. Operation between 40°C and
50°C requires output current de-rating. Rated output current must be de-rated for 1.5% per 1°C
temperature rise. Permissible maximum temperature is 50°C.
■
Altitude De-rating
The drive must be de-rated for an installation altitude of above 1000 meters because cooling
effect available from ambient air reduces. Rated output current must be de-rated for 1% per 100
meters. Maximum altitude is 3000 meters.
1
Summary of Contents for GT600-4T132G
Page 1: ...GT600 AC Drive...
Page 5: ......
Page 86: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 86 5 2 Setup Flowchart 87...
Page 87: ......
Page 100: ...5 Quick Setup 98 5...
Page 280: ...8 Peripherals and Options 278 8...
Page 306: ...12 303 11...
Page 362: ......