19
Disconnect all devices before stopping the generator! Do not stop the
generator if it has any devices connected to it.
This may disable the generator!
Connecting Power Consumers
After switching on the generator, make sure that the voltmeter readings correspond to
the nominal ones (230 V +/-5% @ 50 Hz for single-phase generator and 400 V +/-5%
50 Hz for three-phase generator).
KS 14100 HDE 1/3 ATSR та KS 14200 HDES 1/3 ATSR
diesel generator models are suitable for 230 V power consumers
(single-phase generators) and 400 V power consumers (three-
phase generators). Mode switching is allowed only when no power
consumers are connected.
Using as a three-phase generator:
The three-phase diesel generator should have the power distributed to all three
phases, and the power must be balanced at all phases. The power at each of the three
phases must not exceed 1/3 of the total power of the generator. The balance tolerance
should not exceed 20%.
If only 1 or 2 phases are loaded, the generator will fail. The total power and total current
at all three phases must not exceed the normal load and amperage of the generator.
Failure to comply with these requirements may damage the primary
and secondary windings and the AVR unit.
If the overload resulted in automatic operation of the generator
circuit breaker, reduce the load. Repeated power-on of the generator
is possible 5 minutes after disabling.
NOTE!
Do not operate single-phase and three-phase circuit breakers at
the same time to prevent electric shock and avoid damage to your
electrical devices and the generator!
(Circuit breakers are shown in Figs. 3 and 4)
IMPORTANT!
IMPORTANT!
IMPORTANT!