KT-MOD-INP16

KT-400 Expansion Module 16-Zone Input with SPI Cable Install Sheet

 
 
 
 
 
 

4. Configurations 

with 

Jumpers 

There are 3 jumpers available to configure the KT-MOD-INP16. 

The jumper settings apply to 

ALL

 16 inputs at the same time. 

Note

: Jumper JP4 is for future use. 

DRY (without end-of-line resistor):

 In a simple NC dry contact 

configuration, the 

secure

 state is given when a short is detected. 

The voltage becomes lower than the 

Level 1

 threshold value 

(1.1V).  
The 

alarm

 state is given when the input is open. The voltage 

becomes higher than the 

Level 2

 threshold value (3.75V). If the 

alarm switch is programmed as NO device, the 

alarm

 state will 

be given when the input is shorted. 

EOL (with end-of-line resistor):

 For NC device, the 

secure

 

state is given when a single resistor is detected. The voltage 

becomes lower than the 

Level 3

 threshold value (2.9V) and 

higher than the 

Level 2

 threshold value (2.25V).  

The 

alarm

 state is given when the input is open or short. The 

voltage becomes higher than the 

Level 4

 threshold value (3.75V) 

or lowers than the 

Level 1

 threshold value (1.1V). If the alarm 

switch is programmed as NO device, the 

alarm

 state will be given 

when a single resistor is detected. 

5. 

Applying Power

 

After all wiring is completed, connect the 16 VAC to the KT-400. 

Connect the battery leads to the battery, and then apply power to 

the AC transformer. 

Note

: Do not connect power until all wiring is complete. 

 

 

 

Terminal Connections 

Module no.: ______________________________________________________________________________________  
Date of installation: _______________________________________________________________________________  
KT-400 Name: ____________________________________________________________________________________  
KT-400 SITE NAME: _______________________________________________________________________________  
KT-400 Serial Number: _____________________________________________________________________________  
AUX: ___________________________________________________________________________________________  
SPI BUS (FROM): _________________________________________________________________________________  
SPI BUS (TO): ____________________________________________________________________________________  

F

 Z1:  

 

F

 Z9: __________________________________________  

F

 Z2:  

 

F

 Z10: _________________________________________  

F

 Z3:  

 

F

 Z11: _________________________________________  

F

 Z4:  

 

F

 Z12: _________________________________________  

F

 Z5:  

 

F

 Z13: _________________________________________  

F

 Z6:  

 

F

 Z14: _________________________________________  

F

 Z7:  

 

F

 Z15: _________________________________________  

F

 Z8:  

 

F

 Z16: _________________________________________  