4.2.2 BACnet Broadcast Management Device (BBMD)
If the “BACnet Workstation Operator “ or other BACnet device which needs to establish a bind with the
“M-Bus:BACnet Gateway” is located on a different IP sub-network, you have to register the device IP
number in the “BBMD Registration dialog”. The default port is 47808 (bac0 in hexadecimal). Enter the
new IP Number in the “IP Number Field” and click on save to register this remote device IP number.
4.3 BACnet Objects
BACnet Objects are not automatically included. By M-Bus Gateway you have to select the checkbox “to
BACnet” for the particular meter record or records.
For Modbus Gatway select the check box “to BACnet in the modbus object configuration. The BACnet
Instance number and type is done automatically.
4.4 M-Bus Configuration