The M-Bus:BACnet Gateway is a BACnet Application Specific Controller (B-ASC)
The selected M-Bus Meter Records will converted to BACnet Analog Objects
A B-ASC intended for use in a specific application and supports limited programmability. It enables
specification of the following:
•
Ability to provide the values of any of its BACnet objects
•
Ability to allow modification of some or all of its BACnet objects by another device
Management
•
Ability to respond to queries about its status
•
Ability to respond to requests for information about any of its objects
•
Ability to respond to communication control messages
•
Ability for Change-Of-Value subscription
•
Ability to generate Alarm and Event Notification
•
No Trending
•
No Scheduling
The Device will support following BACnet Features:
BIBB = BACnet INTEROPERABILITY BUILDING BLOCKS
•
BIBB-Data Sharing-ReadProperty-B (DS-RP-B)
•
BIBB - Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)
•
BIBB - Data Sharing-WriteProperty-B (DS-WP-B)
•
BIBB - Data Sharing-COV-B (DS-COV-B)
•
BIBB - Device Management-Dynamic Device Binding-B (DM-DDB-B)
•
BIBB - Device Management-Dynamic Object Binding-B (DM-DOB-B)
•
BIBB - Device Management-DeviceCommunicationControl-B (DM-DCC-B)
•
BIBB - Device Management-UTCTimeSynchronization-B (DM-UTC-B)
•
BIBB - Device Management-TimeSynchronization-B (DM-TS-B)
•
BIBB - Alarm and Event-Notification Internal-B (AE-N-I-B)
•
BIBB - Alarm and Event-ACK-B (AE-ACK-B)
•
BIBB - Device Management-Object Creation and Deletion-B (DM-OCD-B)
(only for Notification Class Object)
Supporter Objects:
•
Device
•
Binary Inputs and Output for modbus coils and descrete Inputs
•
Analog Inputs and Outputs for Meter readings, modbus registers and holding registers
•
Notifications Class