2
몇
Warning
Possible hazardous situation that could
lead to severe injury or even death.
Caution
Possible hazardous situation that could
lead to mild injury to persons or damage to
property.
The plant is used for treating surface water
and water from natural springs.
The raw water should have a maximum salt
content of 2000 mg/l (FW model) or 5000
mg/l (BW model).
Due to the modular structure, turbid sub-
stances, hardeners, salts, bacteria and wa-
ter can be separated depending on the
quality of raw water.
Notes about the ingredients (REACH)
You will find current information about the
ingredients at:
www.kaercher.com/REACH
Danger
Risk of injury if the plant is not installed
properly. Risk to health on account of poor-
ly treated drinking water. The plant may be
put into operation only when set-up, in-
stalled and prepared for operation by
skilled and authorized personnel.
Check the connection of the plant to the
raw water source.
Ensure uninterrupted flow of the gener-
ated drinking water into a tank or a suit-
able user-side facility.
Note
The drinking water must be able to flow out
without any counter-pressure. The height
difference must not be more than 3 m.
Note
If an advance pressure unit is required,
then the same would be installed by the
Kärcher service technician.
1 Pump
2 Controlling device
3 LED green: operations stand-by
4 LED yellow: pump is transporting water
5 LED red: interruption or water shortage
Note
If the plant is fitted with one or more dosing
stations, then it needs to be ensured that
this has been connected properly and filled
up.
Fill up dosing station (refer chapter
"Maintenance and Care/ Maintenance
jobs")
Check whether the mains plug of the
dosing pumps of the dosing stations is
connected to the power supply.
Insert the plug of the unit into the sock-
et.
If a float switch has been connected,
then the plant will start automatically as
soon as the required water quantity is
reached.
If no float switch is connected, switch on
the plant by pressing the "ON/OFF" key
on the operating panel.
–
Display time
Alternating display of:
–
Display for power failure:
This display appears when the connection
to the power supply is lost (for e.g. the plug
has come out of the socket or there is pow-
er failure).
–
Operations stand-by:
–
When the clock has been set, only the
operations stand-by is displayed.
Caution
Risk of damage. If the plant is to be shut
down for more than 14 days, then Kärcher
Customer Service must carry out some
preservative tasks.
Press the "ON/OFF" key; the unit stops
production of drinking water.
Note
Do not switch off the plant overnight! The
media filter is automatically cleaned during
the night. There is a risk of damage to the
plant if you do not do this cleaning.
Danger
Health hazard on account of poor quality of
drinking water. The control tasks outlined in
this maintenance plan are to be carried out
according to the schedule in order to en-
sure the quality of drinking water. If the de-
viations in the target values cannot be
corrected by taking the prescribed meas-
ures, then stop production of drinking water
and inform Kärcher Customer Service im-
mediately.
Use as intended
Environmental protection
The packaging material can be
recycled. Please do not place
the packaging into the ordinary
refuse for disposal, but arrange
for the proper recycling.
Old appliances contain valuable
materials that can be recycled.
Please arrange for the proper re-
cycling of old appliances. Batter-
ies, oil, and similar substances
must not enter the environment.
Please dispose of your old appli-
ances using appropriate collec-
tion systems.
Start up
Before Commissioning
Advance pressure unit
Filling up the dosing station
Operation
Switching on the plant
Monitoring elements
Display media and active carbon filters
Display of the operating panel
Spannungsausfall
Uhr stellen !
Power failure
Set clock !
Arret secteur
L'horloge placer
mancan. corrente
regoli l'orolog.
Standby
243
μ
S/cm 21°C
Standby
243
μ
S/cm 21°C
Attente
243
μ
S/cm 21°C
pronto p. lavoro
243
μ
S/cm 21°C
Switching off the plant
Maintenance and care
13
EN
Summary of Contents for WPC 600 BW
Page 2: ...2...
Page 64: ...8 WPC B 1 024 dH C S cm h MPa MPa MPa l h S cm ____ 64 EL...
Page 65: ...9 WPC A 1 024 h dH S cm pH pH C MPa MPa MPa MPa MPa MPa MPa MPa l h l h S cm K rcher 65 EL...
Page 83: ...9 WPC B 1 024 dH C a a ____ 83 RU...
Page 84: ...10 WPC A 1 024 dH pH pH C M a M a M a M a M a M a a a Antiscalant rcher 84 RU...
Page 94: ......
Page 95: ......