5
Close the cover of the dosing station.
Pull out the mixing rod from the dosing
container until the stop and push it back
into the container.
Repeat this process for approx. 5 min-
utes until the chemicals are fully mixed.
Deaerate the dosing pump according to
the instructions in the chapter "Mainte-
nance and Care".
Partially emptied dosing container:
Check the filling level of the dosing con-
tainer, for e.g. 35 l.
Determine the refill quantity - subtract
the filling level value you have read
from 75 l. In the example: 75 l – 35 l =
40 l.
From the dosing table, find out the re-
quired quantity of the corresponding
chemicals. In the example: 4 times the
quantity for 10 l water.
Measure the ascertained quantity of the
corresponding chemical and fill it into
the dosing container.
Fill up the dosing container up to the
mark "75 l" with chlorine-free water.
Close the cover of the dosing station.
Pull out the mixing rod from the dosing
container until the stop and push it back
into the container.
Repeat this process for approx. 5 min-
utes until the chemicals are fully mixed.
The LEDs on the operating panel will dis-
play the interruptions in the RO plant.
Note
If there is an interruption, the plant gets
switched off automatically and the drinking
water production is interrupted. If the prob-
lem cannot be rectified, switch off the plant
and inform Kärcher Customer Service.
If the plant does not start automatically,
pull the plug out of the socket, wait for 5
seconds and insert back the plug. The
controls will get reset.
Rectify other faults according to the de-
tails provided in the following tables.
Consumables
Description
Order No.
RM 852 Sterilisation
agent
Calcium hyprochlorite
RM 5000 Hardness sta-
biliser
RM 5001 Flocking agent
Filter inlay for fine filter,
5
μ
m
6.640-014.0
Faults
Interruptions in the RO plant
LED
glows
Display
Possible cause
Remedy
Mainte-
nance
Maintance spools have been triggered manually. Wait for the end of rinsing process.
CD
CD Permeat Max
CD Permeate Max
CD permeat max.
CD permeaz. mas.
Guide value of drinking water is too high.
Inform Customer Service.
Fault
Water shortage
Low water press.
Manque d'eau
mancanza acqua
Pressure of raw water is too low.
Check raw water supply:
–
Installation in the building
–
Advance pressure pump
–
Fine filter status (see "Maintenance tasks"
Motorschutz
Motor protect
Protection mot.
protezione moto.
–
Motor protection switch of the high pressure
pump has got released.
–
HP pump is overheated
–
Dosing container is empty
Check condition
–
Motor protection switch
–
Filling quantity for all dosing containers
CD MB überschritten
Exceed range CD
P. mes. depassee
eccedi l.gammaCD
Measuring range of the conductivity probe ex-
ceeded
Inform Customer Service.
Frostgefahr
Temperature low
Risque de gelee
pericolo di gelo
Water temperature below 1 °C
Ensure freedom from frosting
–
Standby
Standby
Attente
pronto p. lavoro
Drinking water tank is full.
Nothing needs to be done; the plant will start
automatically
Rinse
Flush
Lavage
risciacquo
Automatic flush is active
LED
glows
Display
Possible cause
Remedy
Stop
Stop
Arret
arresto
Regeneration of media or active carbon filter is
active
Nothing needs to be done; the plant will start
automatically
16
EN
Summary of Contents for WPC 600 BW
Page 2: ...2...
Page 64: ...8 WPC B 1 024 dH C S cm h MPa MPa MPa l h S cm ____ 64 EL...
Page 65: ...9 WPC A 1 024 h dH S cm pH pH C MPa MPa MPa MPa MPa MPa MPa MPa l h l h S cm K rcher 65 EL...
Page 83: ...9 WPC B 1 024 dH C a a ____ 83 RU...
Page 84: ...10 WPC A 1 024 dH pH pH C M a M a M a M a M a M a a a Antiscalant rcher 84 RU...
Page 94: ......
Page 95: ......