Installation Manual Kardia Alta
/
40
Blind cover and cable entries
Openings in cover plates should be covered after installation.
High voltage: 26x ø16mm, 8x ø20mm, 1x ø50mm.
Low voltage: 5x ø16mm, 23x ø20mm, 2x ø25mm.
From the bottom: 3x ø50mm.
Documentation / Labelling
The circuit list is glued on the inside of the door, other
documents are delivered to the owner. The supplied label
for
voltage, network type, main circuit breaker, gauge and circuit
number are attached to front plate.
Kardia's electrical panel is equipped with CHINT overload
protection and earth fault devices.
Main circuit breaker (4P 40A 10kA or 3P 50A 10kA)
The overload protection is made of halogen-free material. Should
it be connected to aluminum, transitions must be used.
Icu=10/15kA, Ics=10kA, Icn=10kA. Ue=230/400V, Ui=500V, 50/60Hz.
Cleaning: No specific cleaning requirements. Avoid using water.
Energy consumption: Less than 5W/pole.
Procedures: Functionality test and check for overheating approx.
once per year.
Electrical lifetime: 8000 cycles.
Mechanical lifetime: 20000 cycles.