• Avoid installation of sensors in the vicinity of deformations and pipe

defects, near welding seams or where deposits could have accumu-

lated.

• Select a measuring point with sufficient straight pipe to obtain ac-

curate measurements. Please consult the manual for the recom-

mended distances from sources of disturbance.

• For a horizontal pipe, mount the sensors on the side of the pipe. For

a vertical pipe, mount the sensors at a location where the liquid

flows upwards (Pic. 1).

• Mount the sensors in the direction of the flow (Pic. 2).

• Clean the pipe at the measurement point. Remove loose paint and

rust with a wire brush or file.

• Apply coupling paste to the face of the clamp-on sensors before

attaching them to the pipe.

Select

Setup Wizard CH1 to set up the

measurement channel 1, or

CH2 for

channel 2. Confirm selection by pres-

sing

ENTER. If the sensors are recog-

nised, the serial number will be shown.

Ifnot, the type can be selected.

1. Mounting points

2. Flow direction

Sensor Mounting Configuration

Reflection Mode

The flowmeter uses an even number

of passes. This is the most conveni-

ent mounting arrangement, as the

transducer separation distance can

be measured very easily and the

sensors can be accurately aligned.

Use whenever possible (Pic. 3).

3. Reflection mode (from above)

Diagonal Mode

Signal travels on an odd number of

passes through the pipe. A single

pass can be used for larger pipes

and for dirty/aerated liquids where

greater signal attenuation can occur.

The sensor distance on this moun-

ting configuration can be negative

(sensors overlapping) (Pic. 4).

Step 3: Quick Start Menu and Setup Wizard

At first power on and the boot se-

quence, the

Main Menu is displayed.

Use the

UP and DOWN cursor keys to

select

Quick Start and confirm by

pressing

ENTER.

Enter the fluid temperature using the

keypad. Confirm by pressing

ENTER.

Use

UP key as a backspace to correct

for entry errors.

Select fluid using cursor keys. Con-

firm by pressing

ENTER.

Enter pipe wall thickness using the

keypad and confirm with

ENTER. Use

UP key as a backspace to correct for

entry errors.

Enter the outer pipe diameter us-

ing the keypad and confirm with

ENTER. Use UP key as backspace to

correct for entry errors. If "0" is entered

and confirmed, an additional screen

appears that allows entry of the cir-

cumference. Press

ENTER to confirm.

Select the pipe material using the cur-

sor keys and confirm with

ENTER.

Select the main measurement unit

using the cursor keys and confirm

with

ENTER. This unit will be dis-

played in the middle of the measure-

ment screen. Selecting

OFF deactivates

the measurement channel.

• Show

NEXT (1) available item

Q

ON

(2) = Start totaliser function

• Show next

DISPlay (3)

Q

OFF

(8) = Stop totaliser function

DIRECT (9) access to trend plot

• Move menu/selection item

UP

• Move menu/selection item

DOWN

ESCape entry without saving

Switch device

OFF (press > 2 sec.)

ENTER selection with saving

Switch device

ON (press > 2 sec.)

Step 1: Measurement Point and Pipe Preparation

4. Diagonal mode (from above)

• The flowmeter can be prepared for measurement with the

Setup

Wizard as found in the Quick Start menu.

Step 2: Keyboard Familiarisation

Select pipe liner material usingcursor

keys and confirm by pressing

ENTER.

If a liner material is chosen, an additi-

onal screen appears that allows entry

of liner thickness.

KATflow 230

Quick Start Manual