Two way switch
06
www.katusensor.com
! Wiring must be done by a qualified electrician and the national and international
codes for the installation of electrical equipment must be followed.
The supply voltage shall comply with EN 50178, SELV and PELV standards
Cut off the power
Connect the product according to the corresponding wiring method in the figure below
1
5
4
2
3
1
2
3
4
5
brown
white
blue
black
grey
Power
Switch output SP2 (analog)
Power supply -
Switch output SP1 (IO-Link)
Analog output (voltage or current)
NPN
12~30VDC
1
2
4
5
3
brown
white
black
blue
+
-
12~30VDC
PNP
1
2
4
5
3
brown
white
black
blue
+
-
SP1
SP2
SP1
SP2
Two way (IO-Link)
NPN
12~30VDC
1
2
4
5
3
brown
white
black
blue
+
-
12~30VDC
PNP
1
2
4
5
3
brown
white
black
blue
+
-
SP1
SP2
SP1
SP2
Electrical connection
IO-Link
IO-Link
res
factory data reset
Hold down [+] to restore factory Settings
ou1
Pressure value switch 1 signal: (Factory default HNO)
Hysteresis function: HNO (normally open) /HNC (normally closed)
Window function: FNO (normally open) /FNC (normally closed)
Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed:
At the press of a button, the value increases; Hold the button down and the value will keep changing.
ou2
Pressure value switch 2 signal: (Factory default HNC)
Hysteresis function: HNO (normally open) /HNC (normally closed)
Window function: FNO (normally open) /FNC (normally closed)
Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed:
At the press of a button, the value increases; Hold the button down and the value will keep changing.
ds1
The opening delay of OUT1. (The factory default is 0s)
Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed:
At the press of a button, the value increases; Hold the button down and the value will keep changing.
dr1
OUT1 shutdown delay. (The factory default is 0s)
Hold + or [-] for at least 1s. After 1 second: The setting value can be changed:
At the press of a button, the value increases; Hold the button down and the value will keep changing.
ds2
OUT2's opening delay. (The factory default is 0s)
Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed:
At the press of a button, the value increases; Hold the button down and the value will keep changing.
dr2
OUT2 shutdown delay. (The factory default is 0s)
Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed:
At the press of a button, the value increases; Hold the button down and the value will keep changing.
uni
Standard unit of measurement for system pressure (display) : [bar]/[MPa]/[psi]
Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed:
At the press of a button, the value increases; Hold the button down and the value will keep changing.
p-n
PNP/NPN switch (Factory default is PNP)
Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed:
At the press of a button, the value increases; Hold the button down and the value will keep changing.
L0
Historical minimum system pressure.
Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed:
At the press of a button, the value increases; Hold the button down and the value will keep changing.
H0
Maximum system pressure in history
Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed:
At the press of a button, the value increases; Hold the button down and the value will keep changing.
dap
Switch point damping/process data flow (IO-Link communication) and display.
(Factory default: 0.06)