Configuration
B 3.8 Parameter list
This list includes all displayable and alterable parameters.
In the column Change display, the following abbreviations are used:
N = not alterable,
S = alterable only when motor stationary,
I = always alterable, even when motor running
M = display and alterability dependent on
P90-motortype,
P = display only if
P3-param level
is set to
parameter
* = display dependent on other parameters
Par.
Indication Description
Value
range,
Unit
Factory
Change
No.
in display
physical value
setting
display
Basic parameters:
P1
f_rated
Frequency setpoint value control panel 30... 3000
Hz
50
I
P3
Para level
Parameter level
Operation, configuration
-
Operation
I
P4
Display
Standard display
Combi display
, various values
-
Combidisp
.
I
P5
Language
Language of the menu texts
numerical, German, English
-
German
I
P6
F_norm
Standardization factor for P24
0.01... 500.00
-
1.00
I P
P7
Select func.
Operation local, remote control
panel,remote control,parallel
-
Panel
I P
P8
Speed displ
Selection Speed display
in Hz, in min-1
-
in Hz
I P
Display values
P10
f_rated_act
Current frequency setpoint value
0...3000
Hz
-
N
P11
I_limit_act
Current current limit
0.5....12
A~
-
N
P12
f_rated_int
Frequency setpoint value after integrator 0...3000
Hz
-
N
P13
f_out_act
Actual inverter frequency
0..3000
Hz
-
N
P14
f_motor
Actual motor frequency
0...3000
Hz
-
N
P15
V_motor
Output voltage
0..250
V~
-
N
P16
V_DC circ
Intermediate circuit voltage
0..350
V-
-
N
P17
I_mot_app
Apparent motor current
0..12
A~
-
N
P18
I_mot_real
Real motor power
0..12
A~
-
N
P19
P_real
Real power
0..2000
W
-
N
P20
motor code
Motor coding and motor memory
1..8
-
-
N
P24
Norm value
Standardized display value
0...1500000
-
-
N
P25
t_action
Operating hours counter
0... 65000
h
0
N
P26
t_reset
Switch-on time from reset
0... 65000
min
0
N
P30
1st error
Last error
-
-
0
N
P31
2nd error
Penultimate error
-
-
0
N
P32
3rd error
Third-last error
-
-
0
N
P33
4th error
Fourth-last error
-
-
0
N
P34
5th error
Fifth-last error
-
-
0
N
P36
Inverter
Inverter type
-
-
Type 4452
N
P37
SW panel
Firmware version of panel
-
-
-
N
P38
SW mot cont
Firmware version of motor control
-
-
-
N
Motor parameters:
Motor operating values
P41
f_mot_min
Min. motor frequency
30... 100
Hz
50
S P M
P42
f_mot_max
Max. motor frequency
f_mot_nom
, 101 ... 3000
Hz
f_nom
S P
P43
V_mot_max
Max. motor voltage phase-phase
V_mot_nom
, 1 ...250
V~
V_nom
S P
P44
I_limit
Current limitation (phase current)
1.5 * I_mot_nom
, 0,5...12
A~
1,5*I_nom
I P
P46
t_rise
Ramp time for run-up
0.5... 400
s
5
I P
P47
t_fall
Ramp time for fall-down
0.5... 400
s
5
I P
P48
t_stop
Ramp time for stop
DC brake, t_fall
,0.,5..400
s
t_fall
I P
P50
Motor start
Start option, catch circuit
Normal
, catch circuit
-
Normal
I P M
P51
t_start
Start time for microstep operation
without ramp,
0.5 ... 100
s
without ramp
I P M
P52
I_start
Startup current microstep oper. BLDC 0.4 ... 12
A~
0.4
I P M *
P53
f_start
Startup frequency microstep operation 1 ... 30
Hz
5
S P M
P54
t_off
Inverter switch-off time, startup
200 ... 1000
µs
600
S P M
P55
t_DC_brake
DC brake time DC brake
off, 0.1... 120
s
2
I P M
P56
I_DC_brake
DC brake current DC brake
0.1 ... 12
A-
1
I P M *
P57
I_DC_stop
DC stop current (at stop)
off, 0.1 ... 3
A-
off
I P
P58
emerg. stop
Select emergency stop at mains failure
inactive
, on at mains failure
-
inactive
I P
P59
speedsensor
Number of pulses at speed senor
no speed sensor
, 1...10
I/U
no sensor
S P M
31