13.8 Error codes
When a safety device is activated, an error code will be displayed on the user interface.
A list of all errors and corrective actions can be found in the table below.
Reset the safety by turning the unit OFF and back ON.
In case this procedure for resetting the safety is not successful, contact your local dealer.
ERROR
CODE
MALFUNCTION
OR PROTECTION
FAILURE CAUSE
AND CORRECTIVE ACTION
The condenser outlet refrigerant
temperature sensor (T3)error.
1. The T3 sensor connector is loosen. Reconnect it.
2.The T3 sensor connector is wet or there is water in. remove the
water, make the connector dry. Add waterproof adhesive
3. The T3 sensor failure, change a new sensor.
The ambient temperature
sensor (T4) error.
1. The T4 sensor connector is loosen. Reconnect it.
2.The T4 sensor connector is wet or there is water in. remove the
water, make the connector dry. Add waterproof adhesive
3. The T4 sensor failure, change a new sensor.
Suction temperature sensor(Th)
error
1. The Th sensor connector is loosen. Re connect it.
2.The Th sensor connector is wet or there is water in. remove the
water, make the connector dry. Add waterproof adhesive
3. The Th sensor failure, change a new sensor.
Discharge temperature
sensor(Tp) error
1. The Tp sensor connector is loosen. Re connect it.
2.The Tp sensor connector is wet or there is water in. remove the
water, make the connector dry. Add waterproof adhesive
3. The Tp sensor failure, change a new sensor.
Communication error between
main control board PCB B and
main control board of hydraulic
module
1.wire doesn’t connect between main control board PCB B and
main control board of hydraulic module. connect the wire.
2.Communication wire sequence is not right. Reconnect the wire in
the right sequence.
3. Whether there is a high magnetic field or high power interfere,
such as lifts, large power transformers, etc.. To add a barrier to
protect the unit or to move the unit to the other place.
Communication error between
inverter module PCB A and
main control board PCB B
1. Whether there is power connected to the PCB and driven board.
Check the PCB indicator light is on or off. If Light is off, reconnect
the power supply wire.
2.if light is on, check the wire connection between the main PCB
and driven PCB, if the wire loosen or broken, reconnect the wire or
change a new wire.
3. Replace a new main PCB and driven board in turn.
Three times P6 protect
Same to P6